153
Monitor display and monitor output signal
Regenerative brake
duty
0.1%
9
9
Pr. 70
Brake duty set in
Pr. 30, Pr. 70
Electronic thermal
relay function load
factor
0.1%
10
10
100%
Displays the thermal cumulative value on
the assumption that the thermal operation
level is 100% (Larger thermal between the
motor thermal and transistor thermal).
Output current peak
value
0.01A
11
11
Pr. 56
Holds and displays the peak value of the
output power monitor.
(Cleared at every start)
Converter output
voltage peak value
0.1V
12
12
200V class 400V Holds and displays the peak value of the
DC bus voltage value.
(Cleared at every start)
400V class 800V
Output power
0.01kW
14
14
Rated inverter
power
2
Displays the power on the inverter output
side
Input terminal status
—
—
—
Displays the input terminal ON/OFF status
on the operation panel.
(
Output terminal
status
—
—
Displays the output terminal ON/OFF
status on the operation panel.
(
Cumulative
energization time
1h
20
—
Adds up and displays the energization time
after inverter shipment.
You can check the numbers of the monitor
value exceeded 65535h with
Pr. 563
.
Reference voltage
output
—
—
21
—
Terminal FM:
Output 1440 pulse/s
Actual operation time
,
1h
23
—
Adds up and displays the inverter operation
time.
You can check the numbers of the monitor
value exceeded 65535h with
Pr. 564
.
Can be cleared by
Pr. 171
.
Motor load factor
0.1%
24
24
200%
Displays the output current value on the
assumption that the rated inverter current
is 100%.
Monitor value = output power monitor
value/rated inverter current 100 [%]
Cumulative power
0.01kWh
25
—
Adds up and displays the power amount
based on the output power monitor.
Can be cleared by
Pr. 170
.
Power saving effect
Variable
according
to
parameters
50
50
Inverter capacity
Displays energy saving effect monitor.
You can change the monitor to power
saving, average power saving, cost
savings monitor and % display using
parameters.
(For details, refer to page 176)
Cumulative power
saving
51
PID set point
0.1%
52
52
100%
Displays the set point, measured value and
deviation during PID control (
for details)
PID measured value
0.1%
53
53
100%
PID deviation
0.1%
54
—
Inverter I/O terminal
monitor
—
55
—
Displays the ON/OFF status of the inverter
input terminal and output terminal on the
operation panel (
for
details)
Motor thermal load
factor
0.1%
61
61
Thermal relay
operation level
(100%)
Motor thermal heat cumulative value is
displayed.
(Motor overload trip (E.THM) at 100%)
Inverter thermal load
factor
0.1%
62
62
Thermal relay
operation level
(100%)
Transistor thermal heat cumulative value is
displayed.
(Inverter overload trip (E.THT) at 100%)
Types of Monitor
Unit
Pr. 52
Setting
Pr. 54
(FM)
Setting
Terminal FM
Full Scale Value
Description
Operation
panel
LED
PU
main
monitor