247
Communication operation and setting
(6) Modbus registers
System environment variable
The communication parameter values are not cleared.
For write, set the data as a control input instruction.
For read, data is read as an inverter operating status.
For write, set data as the operation mode setting.
For read, data is read as the operation mode status.
Real time monitor
Refer to page 152
for details of the monitor description.
When
Pr .37
= "0.01 to 9998", displayed in integral number. (
for
Pr. 37.
)
Input terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, —: undetermined value)
Output terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, —: undetermined value)
The monitored values are retrained even if an inverter fault occurs. Resetting will clear the retained values.
Register
Definition
Read/write
Remarks
40002
Inverter reset
Write
Any value can be written.
40003
Parameter clear
Write
Set H965A as a written value.
40004
All parameter clear
Write
Set H99AA as a written value.
40006
Parameter clear
Write
Set H5A96 as a written value.
40007
All parameter clear
Write
Set HAA99 as a written value.
40009
Inverter status/control input instruction
Read/write
See below.
40010
Operation mode/inverter setting
Read/write
See below.
40014
Running frequency (RAM value)
Read/write
According to the
Pr. 37
settings, the frequency
and selectable speed are in 1r/min increments.
40015
Running frequency (EEPROM value)
Write
b15
b0
—
—
—
—
—
—
—
—
—
RH
RM
AU
—
—
STR
STF
b15
b0
—
—
—
—
—
—
—
—
—
—
ABC
—
—
—
—
RUN
<
Inverter status/control input instruction
>
The signal within parentheses is the initial setting. Definitions change according to the
Pr. 180 to Pr. 182 (input terminal function selection) (refer to page 134)
.
Each assigned signal is valid or invalid depending on NET.
The signal within parentheses is the initial setting. Definitions change according to the
Pr. 190, Pr. 192 (output terminal function selection) (refer to page140)
.
Bit
Definition
Control input instruction
Inverter status
0
Stop command
RUN (inverter running)
1
Forward rotation command
Forward rotation
2
Reverse rotation command
During reverse rotation
3
RH (high-speed operation
command)
SU (up-to-frequency)
4
RM (middle-speed operation
command)
OL (overload)
5
AU (terminal 4 input selection)
0
6
0
FU (frequency detection)
7
RT (second function selection)
ABC (fault)
8
AU (terminal 4 input selection)
0
9
0
0
10
MRS (output stop)
0
11
0
0
12
0
0
13
0
0
14
0
0
15
0
Fault occurrence
<
Operation mode/inverter setting
>
The restrictions depending on the operation
mode changes according to the computer
link specifications.
Mode
Read Value
Written
Value
EXT
H0000
H0010
PU
H0001
—
EXT
JOG
H0002
—
NET
H0004
H0014
PU+EXT
H0005
—
Register
Description
Unit
40201
Output frequency/speed, machine
speed
0.01Hz/1
40202
Output current
0.01A
40203
Output voltage
0.1V
40205
Output frequency setting/speed
setting, machine speed
0.01Hz/1
40208
Converter output voltage
0.1V
40209
Regenerative brake duty
0.1%
40210
Electronic thermal relay function
load factor
0.1%
40211
Output current peak value
0.01A
40212
Converter output voltage peak value
0.1V
40214
Output power
0.01kW
40215
Input terminal status
—
40216
Output terminal status
—
40220
Cumulative energization time
1h
40223
Actual operation time
1h
40224
Motor load factor
0.1%
40225
Cumulative power
1kWh
40250
Power saving effect
Variable
40251
Cumulative power saving
Variable
40252
PID set point
0.1%
40253
PID measured value
0.1%
40254
PID deviation
0.1%
40261
Motor thermal load factor
0.1%
40262
Inverter thermal load factor
0.1%
40263
Cumulative power 2
0.01kWh
40264
PTC thermistor resistance
0.01k
40277
32-bit cumulative power
(lower 16-bit)
1kWh
40278
32-bit cumulative power
(upper 16-bit)
1kWh
40279
32-bit cumulative power
(lower 16-bit)
0.01kWh/
0.1kWh
40280
32-bit cumulative power
(upper 16-bit)
0.01kWh/
0.1kWh
Register
Description
Unit