![Mitsubishi Electric FR-F700PJ Series Скачать руководство пользователя страница 95](http://html.mh-extra.com/html/mitsubishi-electric/fr-f700pj-series/fr-f700pj-series_instruction-manual_239805095.webp)
90
IPM motor control <IPM>
4.3.4
Adjusting the speed control gain (Pr.820, Pr.821)
<IPM>
The above parameters can be set when
Pr.160 User group read selection
= "0."
(1) Adjusting the speed control gain manually
The speed control gain can be adjusted for the conditions such as abnormal machine vibration, acoustic noise, slow
response, and overshoot.
Actual speed gain is calculated as below when load inertia is applied.
Manual adjustment of gain is useful to exhibit the optimum performance of the machine or to improve unfavorable
conditions such as vibration and acoustic noise during the operation with high load inertia or gear backlashes.
Parameter
Number
Name
Initial
value
Setting
range
Operation
820
Speed control P gain 1
25%
0 to 1000%
The proportional gain during speed control is set.
(Setting this parameter higher improves the trackability
for speed command changes. It also reduces the speed
fluctuation due to a load fluctuation.)
821
Speed control integral time 1
0.333s
0 to 20s
The integral time during speed control is set. (Setting
this parameter lower shortens the return time to the
original speed when the speed fluctuates due to a load
fluctuation.)
Pr.820 Speed control P gain 1
= "25% (initial setting)" is equivalent to
50rad/s (speed response of a single motor). Setting this parameter
higher speeds up the response, but setting this too high causes vibration
and acoustic noise.
Setting
Pr.821 Speed control integral time 1
lower shortens the return time
to the original speed at a speed fluctuation, but setting it too low causes
overshoot.
Actual speed gain = Speed gain of a single
motor
JM
JM: Motor inertia
JL: Load inertia converted as the motor axis inertia
JM+JL
IPM
IPM
IPM
Pr.820
Setting
100%
25%
(Initial setting)
Proportional gain
200rad/s
50rad/s
Setting the proportional gain higher
speeds up the response and reduces the speed fluctuation here.
Load fluctuation
Speed
Setting the integral time lower shortens the return time here.
Содержание FR-F700PJ Series
Страница 13: ...IX MEMO ...
Страница 29: ...16 MEMO ...
Страница 76: ...63 MEMO ...
Страница 299: ...294 MEMO ...
Страница 321: ...316 MEMO ...
Страница 346: ...341 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...