217
Selection of operation mode and operation location
(5) Switching of command source by external signal (X67)
In the Network operation mode, the command source switching signal (X67) can be used to switch the start command
source and speed command source.
Set "67" to any of
Pr. 178 to Pr. 182 (input terminal function selection)
to assign the X67 signal to the control terminal.
When the X67 signal is OFF, the start command source and speed command source are control terminal.
X67 Signal State Start Command Source
Speed Command
Source
No signal
assignment
According to
Pr. 338
According to
Pr. 339
ON
OFF
Command is valid only from control terminal.
REMARKS
The ON/OFF state of the X67 signal is applied only during a stop. It is applied after a stop when the terminal is switched while
the inverter is running.
When the X67 signal is OFF, a reset via communication is disabled.
NOTE
Changing the terminal assignment using
Pr. 178 to Pr. 182 (input terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 59 Remote function selection
Pr. 79 Operation mode selection
Pr. 178 to Pr. 182 (input terminal function selection)