43
EMC and leakage currents
(2) Line-to-line leakage currents
Harmonics of leakage currents flowing in static capacitances between the inverter output cables may operate the external
thermal relay unnecessarily. When the wiring length is long (50m or more) for the 400V class small-capacity model (7.5kW or
less), the external thermal relay is likely to operate unnecessarily because the ratio of the leakage current to the rated motor
current increases.
Line-to-line leakage current data example (400V class)
*The leakage current of the 200V class is about a half.
Measures
Use
Pr. 9 Electronic thermal O/L relay
.
If the carrier frequency setting is high, decrease the
Pr. 72 PWM frequency selection
setting.
Note that motor noise increases. Selecting
Pr. 240 Soft-PWM operation selection
makes the sound inoffensive.
To ensure that the motor is protected against line-to-line leakage currents, it is recommended to use a temperature
sensor to directly detect motor temperature.
Installation and selection of moulded case circuit breaker
Install a moulded case circuit breaker (MCCB) on the power receiving side to protect the wiring of the inverter input side.
Select the MCCB according to the inverter input side power factor (which depends on the power supply voltage, output
frequency and load). Especially for a completely electromagnetic MCCB, one of a slightly large capacity must be selected
since its operation characteristic varies with harmonic currents. (Check it in the data of the corresponding breaker.) As an
earth leakage current breaker, use the Mitsubishi earth leakage current breaker designed for harmonics and surge
suppression.
Motor Capacity
(kW)
Rated Motor
Current (A)
Leakage Current (mA)
*
Wiring length 50m
Wiring length 100m
0.4
1.1
620
1000
0.75
1.9
680
1060
1.5
3.5
740
1120
2.2
4.1
800
1180
3.7
6.4
880
1260
5.5
9.7
980
1360
7.5
12.8
1070
1450
Motor: SF-JR 4P
Carrier frequency: 14.5kHz
Used wire: 2mm
2
, 4 cores
Cabtyre cable
Power
supply
Thermal relay
Line-to-line static
capacitances
MCCB
MC
Line-to-line leakage currents path
Motor
Inverter
M