22
Main circuit terminal specifications
2.2.4
Cables and wiring length
(1) Applicable wire size
Select the recommended cable size to ensure that a voltage drop will be 2% or less.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to
decrease especially at the output of a low frequency.
The following table indicates a selection example for the wiring length of 20m.
Three-phase 200V class (when input power supply is 220V)
Three-phase 400V class (when input power supply is 440V)
The cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of 75°C. Assumes
that the surrounding air temperature is 50°C or less and the wiring distance is 20m or less.
The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C. Assumes that the surrounding
air temperature is 40°C or less and the wiring distance is 20m or less.
(Selection example for use mainly in the United States.)
The recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C. Assumes that the surrounding air
temperature is 40°C or less and the wiring distance is 20m or less.
(Selection example for use mainly in Europe.)
The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, PR, P/+, N/-, P1 and a screw for earthing (grounding). Terminal screw size
for Filterpack (FR-BFP2) is same as the terminal screw size for the inverter.
Screw size for earthing (grounding) the FR-F720PJ-15K is indicated in parentheses.
Screw sizes of the terminals R0, S0, and T0 and the earthing terminal of FR-BFP2-H15K are indicated in parentheses.
For the earthing (grounding) cable size for Filterpack, use the same size as for the inverter.
The line voltage drop can be calculated by the following formula:
Line voltage drop [V]=
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
Applicable Inverter
Model
Terminal
Screw
Size
Tightening
Torque
N
·
m
Crimping
Terminal
Cable Size
HIV Cables, etc. (mm
2
)
AWG
PVC Cables, etc. (mm
2
)
R/L1
S/L2
T/L3
U, V, W
R/L1
S/L2
T/L3
U, V, W
Earthing
(grounding)
cable
R/L1
S/L2
T/L3
U, V, W
R/L1
S/L2
T/L3
U, V, W
Earthing
(grounding)
cable
FR-F720PJ-0.4K, 0.75K
M3.5
1.2
2-3.5
2-3.5
2
2
2
14
14
2.5
2.5
2.5
FR-F720PJ-1.5K, 2.2K
M4
1.5
2-4
2-4
2
2
2
14
14
2.5
2.5
2.5
FR-F720PJ-3.7K
M4
1.5
5.5-4
5.5-4
3.5
3.5
3.5
12
12
4
4
4
FR-F720PJ-5.5K
M5
2.5
5.5-5
5.5-5
5.5
5.5
5.5
10
10
6
6
6
FR-F720PJ-7.5K
M5
2.5
14-5
8-5
14
8
5.5
6
8
16
10
6
FR-F720PJ-11K
M5
2.5
14-5
14-5
14
14
8
6
6
16
16
16
FR-F720PJ-15K
M6
(M5)
4.4
(2.5)
22-6
(14-5)
22-6
(14-5)
22
22
14
4
4
25
25
16
Applicable Inverter
Model
Terminal
Screw
Size
Tightening
Torque
N
·
m
Crimping
Terminal
Cable Size
HIV Cables, etc. (mm
2
)
AWG
PVC Cables, etc. (mm
2
)
R/L1
S/L2
T/L3
U, V, W
R/L1
S/L2
T/L3
U, V, W
Earthing
(grounding)
cable
R/L1
S/L2
T/L3
U, V, W
R/L1
S/L2
T/L3
U, V, W
Earthing
(grounding)
cable
FR-F740PJ-0.4K to 3.7K
M4
1.5
2-4
2-4
2
2
2
14
14
2.5
2.5
2.5
FR-F740PJ-5.5K
M4
1.5
5.5-4
2-4
3.5
2
3.5
12
14
4
2.5
4
FR-F740PJ-7.5K
M4
1.5
5.5-4
5.5-4
3.5
3.5
3.5
12
12
4
4
4
FR-F740PJ-11K
M4
1.5
5.5-4
5.5-4
5.5
5.5
5.5
10
10
6
6
10
FR-F740PJ-15K
M5
(M6)
2.5
(4.4)
8-5
(14-6)
8-5
(14-6)
8
8
5.5
8
8
10
10
10
NOTE
Tighten the terminal screw to the specified torque. A screw that has been tightened too loosely can cause a short circuit or
malfunction. A screw that has been tightened too tightly can cause a short circuit or malfunction due to the unit breakage.
Use crimping terminals with insulation sleeve to wire the power supply and motor.
3
×
wire resistance[m
Ω
/m]
×
wiring distance[m]
×
current[A]
1000
Содержание FR-F700PJ Series
Страница 13: ...IX MEMO ...
Страница 29: ...16 MEMO ...
Страница 76: ...63 MEMO ...
Страница 299: ...294 MEMO ...
Страница 321: ...316 MEMO ...
Страница 346: ...341 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...