Function assignment of external terminal and control
(3) Speed detection hysteresis
(Pr.870)
This function prevents chattering of the speed detection
signals.
When an output frequency fluctuates, the up to frequency
signal (SU) and output frequency detection signals (FU) may
repeat ON/OFF (chatters). Setting hysteresis to the detected
frequency prevents chattering of these signals.
REMARKS
All signals are OFF during DC injection brake.
The output frequency compared with the set frequency changes depending on the control method.
NOTE
Changing the terminal assignment using
Pr.190 and Pr.192 (output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 190, Pr. 192 (output terminal function selection)
(
Pr.870
Pr.42
Output
frequency
(Hz)
ON
ON
ON
FU
OFF
OFF
Example of output frequency detection signal (FU)
REMARKS
Setting a higher value to this parameter slows the
response of frequency detection signals (SU and FU).
Control Method
Compared Output Frequency
V/F control
Output frequency
General-purpose magnetic flux
vector control
Output frequency before slip compensation
IPM motor control
Estimated frequency (actual motor rotation per minute)