Check first when you have a trouble
Parameter
Setting
Pr. 0 Torque boost
setting is improper when V/F control is
used.
Increase
Pr. 0
setting by 0.5% increments while
observing the rotation of a motor.
If that makes no difference, decrease the setting.
Pr. 78 Reverse rotation prevention selection
is set.
Check the
Pr. 78
setting.
Set
Pr. 78
when you want to limit the motor rotation to
only one direction.
Pr. 79 Operation mode selection
setting is wrong.
Select the operation mode which corresponds with input
methods of start command and frequency command.
Pr. 146 Built-in potentiometer switching
setting is improper.
Set
Pr. 146
="1" (initial value) when not using FR-E500
operation panel (PA02).
Bias and gain
(calibration parameter C2 to C7)
settings
are improper.
Check the bias and gain
(calibration parameter C2 to C7)
settings.
Pr. 13 Starting frequency
setting is greater than the
running frequency.
Set running frequency higher than
Pr. 13
.
The inverter does not start if the frequency setting signal
is less than the value set in
Pr. 13
.
Frequency settings of various running frequency (such
as multi-speed operation) are zero.
Especially,
Pr. 1 Maximum frequency
is zero.
Set the frequency command according to the
application.
Set
Pr. 1
higher than the actual frequency used.
Pr. 15 Jog frequency
setting is lower than
Pr. 13 Starting
frequency
.
Set
Pr. 15 Jog frequency
higher than
Pr. 13 Starting
frequency.
Operation mode and a writing device do not match.
Check
Pr. 79, Pr. 338, Pr. 339, Pr. 551,
and select an
operation mode suitable for the purpose.
Start signal operation selection is set by the
Pr. 250 Stop
selection
Check
Pr. 250
setting and connection of STF and STR
signals.
The motor is decelerated to a stop when power failure
deceleration stop function is selected.
When power is restored, ensure the safety, and turn
OFF the start signal once, then turn ON again to restart.
The motor restarts when
Pr. 261
="2".
Performing auto tuning.
When offline auto tuning ends, press
of the
operation panel for the PU operation. For the External
operation, turn OFF the start signal (STF or STR).
This operation resets the offline auto tuning, and the
PU's monitor display returns to the normal indication.
(Without this operation, next operation cannot be
started.)
Automatic restart after instantaneous power failure
function or power failure stop function is activated.
(Performing overload operation during input phase loss
may cause voltage insufficiency, and that may result in
detection of power failure.)
Set
Pr. 872 Input phase loss protection selection
= "1"
(input phase failure protection active).
Disable the automatic restart after instantaneous
power failure function and power failure stop function.
Reduce the load.
Increase the acceleration time if the automatic restart
after instantaneous power failure function or power
failure stop function occurred during acceleration.
IPM motor test operation is selected under IPM motor
control.
Set "30" in
Pr.800 Control method selection
.
Load
Load is too heavy.
Reduce the load.
—
Shaft is locked.
Inspect the machine (motor).
—
Others
Operation panel display shows an error (e.g. E.OC1).
When any fault occurs, take an appropriate corrective
action, then reset the inverter, and resume the
operation.
Check
points
Possible Cause
Countermeasures
Refer
to
page
Содержание FR-F700PJ Series
Страница 13: ...IX MEMO ...
Страница 29: ...16 MEMO ...
Страница 76: ...63 MEMO ...
Страница 299: ...294 MEMO ...
Страница 321: ...316 MEMO ...
Страница 346: ...341 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...