FR-E500 series operation panel (PA02) setting
[Setting with the inverter operation panel without fitting the FR-E500 series operation panel (PA02)]
(a) Method to adjust any point
(to change to 80% from 100%)
Operation Display
1.
Confirm the operation status indicator and
operation mode indicator
The inverter should be at a stop.
The inverter should be in the PU operation mode
(depends on
).
2.
Press
to choose the parameter setting
mode.
3.
Turn
until
appears.
4.
Press
to display
.
5.
Turn
until
appears. Turn the dial to
C25 (Pr. 923) Frequency setting voltage gain (built-in
potentiometer)
6.
Press
to show the analog-to digital
conversion value (%).
7.
Turn
to set gain voltage (%).
"minimum value of the potentiometer is 0%,
maximum value is 100%"
8.
Press
to set.
Flicker...Parameter setting complete!!
(Adjustment completed)
Turn
to read another parameter.
Press
to return to the
indication (step 4).
Press
twice to show the next parameter (
).
REMARKS
By pressing
after step 6, you can confirm the present frequency setting bias/gain setting.
It cannot be confirmed after execution of step 7.
The parameter
number read
previously appears.
C0 to C25 settings
are enabled.
Hz
A
Analog voltage value (%) of built-
in frequency setting potentiometer
Hz
A
The gain frequency is reached
when analog voltage value
(%) of built-in frequency
setting potentiometer is 80%.
REMARKS
The current setting at the instant of turning
is displayed.
Hz
A
Hz
A