3
Product checking and parts identification
SERIAL number check
(2) Filterpack
Filterpack model
Parts name and plate
Enclosed items
* The screw size differs according to capacities. ((H)7.5K or lower: M4×14, (H)11K and (H)15K: M5×20)
Rating plate example
The SERIAL consists of one symbol, two characters indicating production year and month, and six
characters indicating control number.
The last digit of the production year is indicated as the Year, and the Month is indicated by 1 to 9,
X (October), Y (November), or Z (December.)
Symbol Year
Month
Control number
SERIAL (Serial No.)
Name
Description
Quantity Refer to page
Screw for leakage current
countermeasure and spacer
When the earth leakage breaker or earth leakage relay operates
unnecessarily due to leakage current, use this screw as a
countermeasure.
1 for each
Rear panel installation
L-bracket
Enclosed for the 5.5K or higher
1
Screw for inverter rear panel
installation
Use these screws for installation of Filterpack onto the inverter rear
panel.
4
*
FR-BFP2- H K
0.4 to 15 Represents the applicable inverter capacity (kW)
Symbol Applicable power voltage
None
200V class
400V class
H
Installation hole
Inverter rear panel
installation screw hole
Terminal block for commercial power supply connection
Black cable: connect to terminal R, S and T of the inverter
Red cable: connect to terminal P and P1 of the inverter
Green and yellow striped cable: connect to the earth (ground) terminal
Crimping terminals for the inverter connection
Rating plate
Terminal block cover
Filterpack model
Rating
SERIAL number
MODEL
FR-BFP2-H0.4K
BKO-
RATED
SERIAL
MITSUBISHI ELECTRIC CORPORATION
Earth (Ground) terminal