109
Frequency setting by external terminals
(2) Jog operation from PU
Select Jog operation mode from the operation panel and PU (FR-PU04/FR-PU07). Operation is performed only while the
start button is pressed.
Operation Display
1.
Confirmation of the operation status indicator
and operation mode indicator
The monitor mode should have been
selected.
The inverter should be at a stop.
2.
Press
to choose the PU Jog operation
mode.
3.
Press
.
While
is pressed, the motor rotates.
The motor runs at 5Hz. (
Pr. 15
initial value)
Press
4.
Release
Release
[When changing the frequency of PU Jog operation]
5.
Press
to choose the parameter setting
mode.
PRM indicator is lit.
(The parameter number read previously
appears.)
6.
Turn
until
Pr. 15 Jog frequency
appears.
7.
Press
to show the present set value.
(5Hz)
8.
Turn
to set the value to "
".
(10Hz)
9.
Press
to set.
Flicker...Parameter setting complete!!
10.
Perform the operations in steps 1 to 4.
The motor rotates at 10Hz.
Three-phase AC
power supply
Inverter
R/L1
S/L2
T/L3
U
V
W
Operation panel
Motor
Stop