Parameter list
Parameter list
64
4
P
A
RAMETE
R
S
Parameter List
4.2 Parameter list
4.2.1
Parameter list
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used. Set the necessary
parameters to meet the load and operational specifications. Parameter setting, change and check can be made from the
operation panel.
To use the inverter under IPM motor control,
refer to page 83
.
Symbol in the Remarks column
...Specifications differ according to the date assembled.
to check the SERIAL number.
These instruction codes are used for parameter read and write by using Mitsubishi inverter protocol with the RS-485 communication.
(
for RS-485 communication)
"
" indicates valid and "
" indicates invalid of "control mode-based correspondence table", "parameter copy", "parameter clear", and "all parameter clear".
Func-
tion
Parameter
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
Parameter
Remarks
Instruction Code
Control Mode-based
Correspondence Table
Parameter
Read
Write
Extended
Copy
Clear
All
clear
B
a
sic fu
nctions
0
Torque boost
0 to 30%
0.1%
6/4/3/2%
0
00
80
0
1
Maximum frequency
0 to 120Hz
0.01Hz
120Hz
1
01
81
0
2
Minimum frequency
0 to 120Hz
0.01Hz
0Hz
2
02
82
0
3
Base frequency
0 to 400Hz
0.01Hz
60Hz
3
03
83
0
4
Multi-speed setting (high speed)
0 to 400Hz
0.01Hz
60Hz
4
04
84
0
5
Multi-speed setting (middle speed)
0 to 400Hz
0.01Hz
30Hz
5
05
85
0
6
Multi-speed setting (low speed)
0 to 400Hz
0.01Hz
10Hz
6
06
86
0
7
Acceleration time
0 to 3600s
0.1s
5/15s
7
07
87
0
8
Deceleration time
0 to 3600s
0.1s
10/30s
8
08
88
0
9
Electronic thermal O/L relay
0 to 500A
0.01A
Rated
inverter
current
9
09
89
0
DC inje
ction
br
ake
10
DC injection brake operation frequency 0 to 120Hz
0.01Hz
3Hz
10
0A
8A
0
11
DC injection brake operation time
0 to 10s
0.1s
0.5s
11
0B
8B
0
12
DC injection brake operation voltage
0 to 30%
0.1%
4/2%
12
0C
8C
0
—
13
Starting frequency
0 to 60Hz
0.01Hz
0.5Hz
13
0D
8D
0
—
14
Load pattern selection
0, 1
1
1
14
0E
8E
0
JO
G
opera
tion
15
Jog frequency
0 to 400Hz
0.01Hz
5Hz
15
0F
8F
0
16
Jog acceleration/deceleration time
0 to 3600s
0.1s
0.5s
16
10
90
0
—
17
MRS input selection
0, 2, 4
1
0
17
11
91
0
—
18
High speed maximum frequency
120 to 400Hz
0.01Hz
120Hz
18
12
92
0
—
19
Base frequency voltage
0 to 1000V, 8888, 9999
0.1V
9999
19
13
93
0
Accel
erati
on/
deceleration time
20
Acceleration/deceleration reference
frequency
1 to 400Hz
0.01Hz
60Hz
20
14
94
0
St
al
l
pr
event
ion
22
Stall prevention operation level
0 to 150%
0.1%
120%
22
16
96
0
23
Stall prevention operation level
compensation factor at double speed
0 to 200%, 9999
0.1%
9999
23
17
97
0
Parameter
Name
Initial
Value
Setting
Range
Remarks
160
User group read
selection
9999
9999
Only the simple mode parameters can be displayed.
0
Simple mode and extended mode parameters can be
displayed.
REMARKS
indicates simple mode parameters.
The parameters surrounded by a black border in the table allow its setting to be changed during operation even if "0" (initial
value) is set in
Pr. 77 Parameter write selection
.
V/F
V/F
V/F
GP
MFVC
GP
MFVC
GP
MFVC
IPM
IPM
IPM
Содержание FR-F700PJ Series
Страница 13: ...IX MEMO ...
Страница 29: ...16 MEMO ...
Страница 76: ...63 MEMO ...
Страница 299: ...294 MEMO ...
Страница 321: ...316 MEMO ...
Страница 346: ...341 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...