136
Function assignment of external terminal and control
4.11.2 Inverter output shutoff signal (MRS signal, Pr. 17)
(3) Assign a different action for each MRS signal input from communication and external terminal
(
Pr. 17
= "4")
When
Pr. 17
is set to "4", the MRS signal from external terminal (output stop) can be changed to the normally closed (NC
contact) input, and the MRS signal from communication can be changed to the normally open (NO contact) input.
This function is useful to perform operation by communication with MRS signal from external terminal remained ON.
The inverter output can be shut off by the MRS signal. Also, logic for the MRS signal can be selected.
Parameter
Number
Name
Initial Value
Setting Range
Description
17
MRS input selection
0
0
Normally open input
2
Normally closed input
(NC contact input specifications)
4
External terminal: Normally closed input
(NC contact input specifications)
Communication: Normally open input
The above parameter can be set when
Pr. 160 Extended function display selection
= "0". (
(1) Output shutoff signal (MRS signal)
Turning ON the output shutoff signal (MRS) during inverter running
shuts off the output immediately.
Set "24" in any of
Pr. 178 to Pr. 182 (input terminal function selection)
to
assign a function to the MRS signal.
MRS signal may be used as described below.
(a) When mechanical brake (e.g. electromagnetic brake) is used to stop
motor
The inverter output is shut off when the mechanical brake operates.
(b) To provide interlock to disable operation by the inverter
With the MRS signal ON, the inverter cannot be operated if the start
signal is entered into the inverter.
(c) Coast the motor to a stop.
When the start signal is turned OFF, the inverter decelerates the
motor to a stop in the preset deceleration time, but when the MRS
signal is turned ON, the motor coasts to a stop.
(2) MRS signal logic inversion
(Pr. 17)
When
Pr. 17
is set to "2", the MRS signal (output stop) can be changed
to the normally closed (NC contact) input specification. When the MRS
signal turns ON (opens), the inverter shuts off the output.
External MRS
Communication MRS
Pr. 17
Setting
0
2
4
OFF
OFF
Operation enabled
Output shutoff
Output shutoff
OFF
ON
Output shutoff
Output shutoff
Output shutoff
ON
OFF
Output shutoff
Output shutoff
Operation enabled
ON
ON
Output shutoff
Operation enabled
Output shutoff
REMARKS
When using an external terminal to input the MRS signal, the MRS signal shuts off the output in any of the operation modes.
NOTE
Changing the terminal assignment using
Pr. 178 to Pr. 182 (input terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
CAUTION
An IPM motor is a motor with interior permanent magnets. High voltage is generated at motor terminals while
the motor is running. Do not touch motor terminals and other parts until the motor stops to prevent an electric
shock.
Parameters referred to
Pr. 178 to Pr. 182 (input terminal function selection)
MRS signal
Time
STF (STR)
signal
The motor coasts to stop
ON
ON
Setting value "0"
Setting value "2"
(initial value)
Output stop
MRS
SD
Inverter
Output stop
MRS
SD
Inverter