Selection and protection of a motor
4.9.3
Exhibiting the best performance for the motor (offline auto tuning)
(Pr. 71, Pr. 80, Pr. 82 to Pr. 84, Pr. 90, Pr. 96)
<GP MFVC>
The above parameters can be set when
Pr. 160 Extended function display selection
= "0".
Performing IPM parameter initialization automatically sets the rated current of the IPM motor.
...Specifications differ according to the date assembled.
to check the SERIAL number.
The motor performance can be maximized with offline auto tuning.
What is offline auto tuning?
When performing General-purpose magnetic flux vector control, the motor can be run with the optimum operating
characteristics by automatically measuring the motor constants (offline auto tuning) even when each motor constants
differs, other manufacturer's motor is used, or the wiring length is long.
Parameter
Number
Name
Initial Value
Setting Range
Description
71
Applied motor
0
0, 1, 3, 13, 23, 40,
43, 50, 53, 120, 210
By selecting a standard motor or constant-
torque motor, thermal characteristic and motor
constants of each motor are set.
80
Motor capacity
9999
0.4 to 15kW
Applied motor capacity.
9999
V/F control
82
Motor excitation current
9999
0 to 500A
Set motor excitation current (no load current)
9999
Uses the Mitsubishi motor (SF-JR, SF-HR,
SF-JRCA, SF-HRCA) constants.
83
Rated motor voltage
200V class
200V
0 to 1000V
Rated motor voltage (V).
400V class
400V
84
Rated motor frequency
60Hz
10 to 120Hz
Rated motor frequency (Hz).
90
Motor constant (R1)
9999
0 to 50
, 9999
Tuning data
(The value measured by offline auto tuning is
automatically set.)
9999: Uses the Mitsubishi motor (SF-JR, SF-
HR, SF-JRCA, SF-HRCA) constants.
96
Auto tuning setting/
status
0
0
Offline auto tuning is not performed.
11
For General-purpose magnetic flux vector
control
Offline auto tuning is performed without motor
running. (motor constant (R1) only)
21
Offline auto tuning for V/F control (automatic
restart after instantaneous power failure (with
frequency search))
POINT
This function is valid only when a value other than "9999" is set in
Pr. 80
and General-purpose magnetic flux
vector control is selected.
You can copy the offline auto tuning data (motor constants) to another inverter with the PU (FR-PU07).
Even when motors (other manufacturer's motor, SF-JRC, etc.) other than Mitsubishi standard motor (SF-JR
0.4kW or higher), high efficiency motor (SF-HR 0.4kW or higher), and Mitsubishi constant-torque motor (SF-
JRCA 4P, SF-HRCA 0.4kW to 15kW) are used or the wiring length is long (30m or more as a reference), using
the offline auto tuning function runs the motor with the optimum operating characteristics.
Tuning is enabled even when a load is connected to the motor.
As the motor may run slightly, fix the motor securely with a mechanical brake or make sure that there will be no
problem in safety if the motor runs (caution is required especially in elevator). Note that tuning performance is
unaffected even if the motor runs slightly.
Reading/writing/copy of motor constants
(Pr. 90)
tuned by offline auto tuning are enabled.
The offline auto tuning status can be monitored with the operation panel and PU (FR-PU04/FR-PU07).
Do not connect a surge voltage suppression filter (FR-ASF-H/FR-BMF-H) between the inverter and motor.
GP
MFVC
GP
MFVC
GP
MFVC