Causes and corrective actions
Operation panel
indication
E.AIE
FR-PU04
Fault 14
FR-PU07
Analog in error
Name
Analog input fault
Description
Appears if voltage(current) is input to terminal 4 when the setting in
Pr.267 Terminal 4 input selection
and the setting of
voltage/current input switch are different.
Check point
Check the setting of
Pr. 267 Terminal 4 input selection
and voltage/current input switch.
Corrective action
Either give a frequency command by current input or set
Pr. 267 Terminal 4 input selection
, and voltage/current input
switch to voltage input.
Operation panel
indication
E.OS
FR-PU04
FR-PU07
E.OS
Name
Overspeed occurrence
Description
Stops the inverter outputs when the motor speed exceeds the
Pr.374
Overspeed detection level
under IPM motor
control. This protective function is available while the IPM motor control is selected.
Check point
Check that the
Pr.374
Overspeed detection level
value is correct.
Corrective action
Set the
Pr.374
Overspeed detection level
value correctly.
Operation panel
indication
E.PID
FR-PU04
Fault 14
FR-PU07
Fault
PID Signal Error
Name
PID signal fault
Description
If any of PID upper limit (FUP), PID lower limit (FDN), and PID deviation limit (Y48) turns ON during PID control,
inverter shuts off the output. This function is active under the following parameter settings:
Pr.554 PID signal operation
selection
"0 or 10",
Pr.131 PID upper limit
"9999",
Pr.132 PID lower limit
"9999", and
Pr.553 PID deviation limit
"9999". This protective function is not active in the initial setting (
Pr.554
= "0",
Pr.131
= "9999",
Pr.132
= "9999",
Pr.553
= "9999").
Check point
Check if the measured PID value is greater than the upper limit
(Pr.131)
or smaller than the lower limit
(Pr.132)
.
Check if the absolute PID deviation value is greater than the limit value
(Pr.553)
.
Corrective action
Make correct settings for
Pr.131 PID upper limit
,
Pr.132 PID lower limit
,
Pr.553 PID deviation limit
.
(Refer to page 250)
Operation panel
indication
E.SAF
FR-PU04
Fault 14
FR-PU07
Fault
E.SAF
Name
Safety circuit fault
Description
Appears when internal circuits are malfunctioning.
Appears when one of the lines between S1 and SC, or between S2 and SC is opened.
Check point
Check if the shorting wire across the terminals S1 and SC or the terminals S2 and SC is disconnected.
Corrective action
Short across the terminals S1 and SC and the terminals S2 and SC with shortening wires.
NOTE
If protective functions of E.ILF, E.SOT, E.AIE, E.IOH, E.PTC, E.CDO, E.PID and E.SAF are activated when using the FR-
PU04, "Fault 14" is displayed.
Also when the faults history is checked on the FR-PU04, the display is "E.14".
If faults other than the above appear, contact your sales representative.