26
Control circuit specifications
(2) Output signal
(3) Communication
Ty
p
e
Terminal
Symbol
Terminal Name
Description
Rated Specifications
Reference
Page
Relay
A, B, C
Relay output (fault
output)
1 changeover contact output indicates that the inverter
protective function has activated and the output stopped.
Fault: discontinuity across B-C (continuity across A-C),
Normal: continuity across B-C (discontinuity across A-C)
Contact capacity:230VAC
0.3A
(power factor =0.4)
30VDC 0.3A
O
pen collect
or
RUN
Inverter running
Switched Low when the inverter output frequency is equal to
or higher than the starting frequency (initial value 0.5Hz).
Switched High during stop or DC injection brake operation.
(Low is when the open collector output transistor is ON
(conducts). High is when the transistor is OFF (does not
conduct).)
Permissible load 24VDC
(maximum 27VDC) 0.1A
(a voltage drop is 3.4V
maximum when the signal
is ON)
SE
Open collector
output common
Common terminal of terminal RUN.
—
—
Pu
ls
e
FM
For meter
Select one e.g. output frequency
from monitored items.
Not output during inverter reset.
The output signal is proportional to
the magnitude of the
corresponding monitored item.
To set a full-scale value for
monitoring the output frequency
and the output current, set
Pr. 55
and
Pr. 56.
Output item:
Output frequency (initial
setting)
Permissible load current
1mA
1440 pulse/s at 60Hz
(general-purpose motor
control)
1440 pulse/s at 90Hz (IPM
motor control)
Type
Terminal
Symbol
Terminal Name
Description
Reference
Page
Comm
unic
ati
o
n
—
PU connector
With the PU connector, communication can be made through RS-485.
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Communication speed: 4800 to 38400bps
Overall length: 500m
NOTE
The terminals S1, S2, SC, and SO are for manufacturer setting. Do not connect anything to these.
Doing so may cause an inverter failure. Do not remove the shortening wires across the terminals S1 and SC and the
terminals S2 and SC. Removing either shortening wire disables the inverter operation.
Содержание FR-F700PJ Series
Страница 13: ...IX MEMO ...
Страница 29: ...16 MEMO ...
Страница 76: ...63 MEMO ...
Страница 299: ...294 MEMO ...
Страница 321: ...316 MEMO ...
Страница 346: ...341 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...