Parameter list
Parameter list
68
Parameter List
Motor
const
ant
s
80
Motor capacity
0.4 to 15kW, 9999
0.01kW
9999
80
50
D0
0
82
Motor excitation current
0 to 500A, 9999
0.01A
9999
82
52
D2
0
83
Rated motor voltage
0 to 1000V
0.1V
200V/400V
83
53
D3
0
84
Rated motor frequency
10 to 120Hz
0.01Hz
60Hz
84
54
D4
0
90
Motor constant (R1)
0 to 50
, 9999
0.001
9999
90
5A
DA
0
96
Auto tuning setting/status
0, 11, 21
1
0
96
60
E0
0
PU connector
commun
ication
117
PU communication station number
0 to 31 (0 to 247)
1
0
117
11
91
1
118
PU communication speed
48, 96, 192, 384
1
192
118
12
92
1
119
PU communication stop bit length
0, 1, 10, 11
1
1
119
13
93
1
120
PU communication parity check
0 to 2
1
2
120
14
94
1
121
Number of PU communication retries
0 to 10, 9999
1
1
121
15
95
1
122
PU communication check time interval
0, 0.1 to 999.8s, 9999
0.1s
0
122
16
96
1
123
PU communication waiting time setting
0 to 150ms, 9999
1
9999
123
17
97
1
124
PU communication CR/LF selection
0 to 2
1
1
124
18
98
1
—
125
Terminal 2 frequency setting gain
frequency
0 to 400Hz
0.01Hz
60Hz
125
19
99
1
—
126
Terminal 4 frequency setting gain
frequency
0 to 400Hz
0.01Hz
60Hz
126
1A
9A
1
PID oper
ation
127
PID control automatic switchover
frequency
0 to 400Hz, 9999
0.01Hz
9999
127
1B
9B
1
128
PID action selection
0, 20, 21
1
0
128
1C
9C
1
129
PID proportional band
0.1 to 1000%, 9999
0.1%
100%
129
1D
9D
1
130
PID integral time
0.1 to 3600s, 9999
0.1s
1s
130
1E
9E
1
131
PID upper limit
0 to 100%, 9999
0.1%
9999
131
1F
9F
1
132
PID lower limit
0 to 100%, 9999
0.1%
9999
132
20
A0
1
133
PID action set point
0 to 100%, 9999
0.01%
9999
133
21
A1
1
134
PID differential time
0.01 to 10s, 9999
0.01s
9999
134
22
A2
1
—
144
Speed setting switchover
2, 4, 6, 8, 10, 102, 104,
106, 108, 110
1
4
144
2C
AC
1
PU
145
PU display language selection
0 to 7
1
0
145
2D
AD
1
—
146
Built-in potentiometer switching
0, 1
1
1
146
2E
AE
1
Cu
rren
t
detection
150
Output current detection level
0 to 150%
0.1%
120%
150
32
B2
1
151
Output current detection signal delay
time
0 to 10s
0.1s
0s
151
33
B3
1
152
Zero current detection level
0 to 150%
0.1%
5%
152
34
B4
1
153
Zero current detection time
0 to 1s
0.01s
0.5s
153
35
B5
1
—
154
Voltage reduction selection during stall
prevention operation
1, 11
1
1
154
36
B6
1
—
156
Stall prevention operation selection
0 to 31, 100, 101
1
0
156
38
B8
1
—
157
OL signal output timer
0 to 25s, 9999
0.1s
0s
157
39
B9
1
—
160
Extended function display selection
0, 9999
1
9999
160
00
80
2
—
161
Frequency setting/key lock operation
selection
0, 1, 10, 11
1
0
161
01
81
2
Automatic rest
art
function
s
162
Automatic restart after instantaneous
power failure selection
0, 1, 10, 11
1
1
162
02
82
2
165
Stall prevention operation level for
restart
0 to 150%
0.1%
120%
165
05
85
2
Func-
tion
Parameter
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
Parameter
Remarks
Instruction Code
Control Mode-based
Correspondence Table
Parameter
Read
Write
Extended
Copy
Clear
All
clear
V/F
V/F
V/F
GP
MFVC
GP
MFVC
GP
MFVC
IPM
IPM
IPM