215
Selection of operation mode and operation location
(2) Controllability through communication
Controllability through communication in each operation mode is shown below.
Monitoring and parameter read can be performed from any operation regardless of operation mode.
As set in
Pr. 338 Communication operation command source
and
Pr. 339 Communication speed command source (Refer to page 214)
At occurrence of RS-485 communication error, the inverter cannot be reset from the computer.
Enabled only when stopped by the PU. At a PU stop, PS is displayed on the operation panel. As set in
Pr. 75 PU stop selection
.
Some parameters may be write-disabled according to the
Pr. 77 Parameter write selection
setting and operating status.
Some parameters are write-enabled independently of the operation mode and command source presence/absence. When
Pr. 77
= "2", write is enabled.
(Refer to the parameter list on
) Parameter clear is disabled.
Available with multi-speed setting and terminal 4-5 (valid when AU signal is ON).
(3) Operation at error occurrence
Can be selected using
Pr. 75 Reset selection/disconnected PU detection/PU stop selection.
Can be selected using
Pr. 122 PU communication check time interval
.
In the PU JOG operation mode, operation is always stopped when the PU is disconnected. Whether fault (E.PUE) occurrence is allowed or not is as set in
Pr. 75 Reset selection/disconnected PU detection/PU stop selection
.
Operation
Location
Condition
(
Pr. 551
Setting)
Operation
Mode
Item
PU
Operation
External
Operation
External/PU
Combined
Operation Mode 1
(
Pr. 79
= 3)
External/PU
Combined
Operation Mode 2
(
Pr. 79
= 4)
NET Operation
Control by
RS-485
communication
from PU
connector
2
(PU connector)
Run command (start)
Run command (stop)
Running frequency
setting
Parameter write
Inverter reset
Other than the
above
Run command (start)
Run command (stop)
Running frequency
setting
Parameter write
Inverter reset
Control circuit
external
terminals
—
Inverter reset
Run command
(start, stop)
Frequency setting
: Enabled,
: Disabled,
: Some are enabled
Error Definition
Operation
Mode
Condition
(
Pr. 551
setting)
PU Operation
External
Operation
External/PU
Combined
Operation Mode
1
(
Pr. 79
= 3)
External/PU
Combined
Operation Mode
2
(
Pr. 79
= 4)
NET Operation
Inverter
fault
—
Stop
PU
disconnection of
the PU
2 (PU connector)
9999 (automatic
recognition)
Stop/continued
Other than the
above
Stop/continued
RS-485
communication
error of the PU
connector
2 (PU connector)
Stop/
continued
Continued
Stop/continued
—
Other than the
above
Continued
Stop/continued