Special operation and frequency control
(11) Bias and gain calibration for PID displayed values (
C42(Pr. 934) to C45(Pr. 935)
)
When both of
C42(Pr. 934)
and
C44(Pr. 935)
"9999", bias/gain calibration is available for analog value of set
point, measured value, deviation value to perform PID control.
"Bias" / "gain" function can adjust the relation between PID displayed coefficient and measured value input
signal. Examples of measured value input signals are 0 to 5VDC, 0 to 10VDC, or 4 to 20mADC, and they are
externally input.
Set PID display bias coefficient for terminal 4 input with
C42(Pr.934)
.
(Initial value is the coefficient for 4mA.)
Set PID display gain coefficient for 20mA of the frequency command current (4 to 20mA) with
C44(Pr. 935)
.
When both of
C42(Pr. 934)
and
C44(Pr. 935)
"9999" and
Pr. 133
is set as the set point, the setting of
C42(Pr.
934)
is treated as 0%, and
C44(Pr. 935)
as 100%.
Three methods of bias/gain adjustment for PID displayed values are the following.
(a)Method to adjust any point by application of voltage (current) across the terminals 4 and 5.
(b)Method to adjust any point without application of voltage (current) across terminals 4 and 5.
(c)Method to adjust only the frequency without adjusting the voltage (current).
(For the detail of (a) to (c),
refer to page 188
.
Make adjustment by assuming
C7 (Pr. 905)
as
C45 (Pr. 935)
, and
Pr. 126
as
C44 (Pr. 935)
.)
NOTE
If the multi-speed (RH, RM, RL, REX signal) or Jog operation (JOG signal) is entered with the X14 signal ON, PID
control is stopped and multi-speed or Jog operation is started.
If the setting is as follows, PID control becomes invalid.
Pr. 79 Operation mode selection
="6" (Switchover mode)
The inverter is at a stop with
Pr. 261 Power failure stop selection
selected.
Changing the terminal function using any of
Pr. 178 to Pr. 182, Pr. 190 and Pr. 192
may affect the other functions.
Set parameters after confirming the function of each terminal.
When PID control is selected, the minimum frequency is the frequency set in
Pr. 902
and the maximum frequency is
the frequency set in
Pr. 903
.
(
Pr. 1 Maximum frequency
and
Pr. 2 Minimum frequency
settings are also valid.)
The remote operation function is invalid during PID operation.
When the control is switched to PID control during normal
operation, the frequency command value calculated by PID
operation using 0Hz as standard is used without the
frequency during the operation.
NOTE
When the voltage/current input specifications are changed with voltage/current input switch and using
Pr. 73
and
Pr.
267
, be sure to make calibration.
PID action
Frequency
command
PID set point
Frequency command
during normal operation
ON
Operation when control is switched to PID control
during normal operation
PID operation
Normal
operation
Normal
operation
100
0
Frequency setting signal
100%
Initial value
Bias
C42(Pr.934)
Gain
C44(Pr.935)
0
20
4
20mA
Coef
ficient
C43(Pr.934)
C45(Pr.935)
Содержание FR-F700PJ Series
Страница 13: ...IX MEMO ...
Страница 29: ...16 MEMO ...
Страница 76: ...63 MEMO ...
Страница 299: ...294 MEMO ...
Страница 321: ...316 MEMO ...
Страница 346: ...341 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...