Special operation and frequency control
(3) Regeneration avoidance function adjustment
(Pr. 665, Pr. 886)
If the frequency becomes instable during regeneration avoidance operation, decrease the setting of
Pr. 886 Regeneration
avoidance voltage gain
. Reversely, if sudden regeneration causes an overvoltage alarm, increase the setting.
When vibration is not suppressed by decreasing the
Pr. 886
setting, set a smaller value in
Pr. 665 Regeneration avoidance
frequency gain
.
REMARKS
The acceleration/deceleration ramp while the regeneration avoidance function is operating changes depending on the
regeneration load.
The DC bus voltage of the inverter is about
times of normal input voltage. (However, it varies with the input power supply
waveform.)
When the input voltage is 220VAC, bus voltage is approximately 311VDC.
When the input voltage is 440VAC, bus voltage is approximately 622VDC.
The
Pr. 883
setting should be kept higher than the DC bus voltage level. Otherwise, the regeneration avoidance function is
always ON even in the non-regeneration status and the frequency increases.
While overvoltage stall (
) is activated only during deceleration and stops the output frequency, the regeneration avoidance
function is always ON (
Pr. 882
= 1) or activated only during a constant speed (
Pr. 882
= 2) and increases the frequency
according to the regeneration amount.
(2) Limit regeneration avoidance operation frequency
(Pr. 885)
You can limit the output frequency compensated (increased) by the
regeneration avoidance function.
The frequency is limited to the output frequency (frequency prior to
regeneration avoidance operation) +
Pr. 885 Regeneration avoidance
compensation frequency limit value
during acceleration or constant speed.
If the regeneration avoidance frequency exceeds the limit value during
deceleration, the limit value is held until the output frequency falls to 1/2
of
Pr. 885
.
When the frequency increased by regeneration avoidance function has
reached
Pr. 1 Maximum frequency
, it is limited to the maximum frequency.
When
Pr. 885
is set to "9999", regeneration avoidance function operation
frequency setting is invalid.
NOTE
The regeneration avoidance function is disabled in the low-speed range (6.5Hz or lower frequency command) under
IPM motor control.
When regeneration avoidance operation is performed,
(overvoltage stall) is displayed and the OL signal is
output. Set the operation pattern at an OL signal output using
Pr. 156
Stall prevention operation selection
. Set the output
timing of the OL signal using
Pr. 157
OL signal output timer
.
When regeneration avoidance operation is performed, stall prevention is also activated at the same time.
The regeneration avoidance function cannot shorten the actual deceleration time taken to stop the motor. The actual
deceleration time depends on the regeneration energy consumption capability. To shorten the deceleration time,
consider using the regeneration unit (FR-BU2, FR-CV, FR-HC2) and brake resistor (MRS type, MYS type, FR-ABR etc.)
to consume regeneration energy at constant speed.
When using the regeneration unit (FR-BU2, FR-CV, FR-HC2) and brake resistor (MRS type, MYS type, FR-ABR etc.),
set
Pr. 882
to "0 (initial value)" (regeneration avoidance function invalid). When using the regeneration unit, etc. to
consume regeneration energy at deceleration, set
Pr. 882
to "2" (regeneration avoidance function valid only at a
constant speed).
Parameters referred to
Pr. 1 Maximum frequency
Pr. 8 Deceleration time
Pr. 22 Stall prevention operation level
2
Limit level
Time
Pr. 885
Output frequency (Hz)
Output frequency (Hz)
Pr. 885
/2
Содержание FR-F700PJ Series
Страница 13: ...IX MEMO ...
Страница 29: ...16 MEMO ...
Страница 76: ...63 MEMO ...
Страница 299: ...294 MEMO ...
Страница 321: ...316 MEMO ...
Страница 346: ...341 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...