127
Selection and protection of a motor
(3) Execution of tuning
1) To perform tuning for PU operation, press
on the operation panel or
or
on the parameter unit (FR-
PU04/FR-PU07).
For External operation, turn ON the run command (STF signal or STR signal). Tuning starts.
(Excitation noise is produced during tuning.)
2) Monitor is displayed on the operation panel and parameter unit (FR-PU04/FR-PU07) during tuning as below.
POINT
Before tuning, check the monitor display of the operation panel or parameter unit (FR-PU04/FR-PU07) to confirm
that the inverter is in the suitable condition for tuning. (Refer to 2) below.) Turning ON the start command in a
tuning-disabled status starts the motor running.
REMARKS
Satisfy the required inverter start conditions to start offline auto tuning. For example, stop the input of MRS signal.
To force tuning to end, use the MRS or RES signal or press
of the operation panel. (Turning the start signal (STF
signal or STR signal) OFF also ends tuning.)
During offline auto tuning, only the following I/O signals are valid: (initial value)
Input terminal <valid signal>
STF, STR
Output terminal
RUN, FM, A, B, C
Note that the progress status of offline auto tuning is output in five steps from FM when speed and output frequency are
selected.
Do not perform ON/OFF switching of the second function selection signal (RT) during execution of offline auto tuning.
Auto tuning is not executed properly.
NOTE
Since the RUN signal turns ON when tuning is started, caution is required especially when a sequence which
releases a mechanical brake by the RUN signal has been designed.
When executing offline auto tuning, input the run command after switching ON the main circuit power (R/L1, S/L2, T/
L3) of the inverter.
When
Pr.79
= "7," turn ON the X12 signal, and tune in the PU operation mode.
Parameter Unit (FR-PU04/FR-PU07)
Display
Operation Panel Indication
Pr. 96
setting
11
11
(1) Setting
(2)Tuning in progress
(3)Normal end
(4)Error end
(when inverter protective
function operation is
activated)
REMARKS
It takes approximately 9s until tuning is completed.
The set frequency monitor displayed during the offline auto tuning is 0Hz.
STOP
PU
11
READ:List
FWD PU
12
STF
TUNE
STOP PU
13
STF
TUNE
COMPETION
Flickering
STOP PU
9
STF
TUNE
ERROR