Quick Start Guide of CV10- ControlVIT Series
1 / 5
EL086A01
❶
Safety precautions
Do not refit the inverter unauthorizedly; otherwise fire, electric shock or other injury may occur.
Please install the inverter on fire-retardant material and keep the inverter away from combustible materials.
Connect the braking optional parts according to the wiring diagram.
Do not operate on the inverter if there is any damage or components loss to the inverter.
Do not touch the inverter with wet items or body, otherwise electric shock may occur.
Only qualified electricians are allowed to operate on the inverter.
Do not carry out any wiring and inspection or changing components when the power supply is applied. Ensure all input power supply is disconnected before wiring and checking and
always wait for at least the time designated on the inverter (5 minutes) or until the DC bus voltage is less than 36V.
❷
Unpacking inspection
Check as followings after receiving products:
1. Check that there are no damage and humidification to the package. If not, please contact with our company.
2. Check the information on the type designation label on the outside of the package to verify that the drive is the correct type. If not, please contact with our company.
3. Check that there are no signs of water in the package and no signs of damage or breach to the inverter. If not, please contact with our company.
4. Check the information on the type designation label on the outside of the package to verify that the name plate is the correct type. If not, please contact with our company.
5. Check to ensure the accessories (including user’s manual and control keypad) inside the device is complete. If not, please contact with our company.
❸
Installation
●
Installation environment
The installation environment is the safeguard for a full performance and long-term stable functions of the inverter. Check the installation environment as followings:
Environment
Conditions
Installation site
Indoor
Environment
temperature
0
℃
~
+
40
℃
, and the temperature changing rate is less than 0.5
℃
/minute.
If the ambient temperature of the inverter is above 40
℃
, derate 3% for every additional 1
℃
.
It is not recommended to use the inverter if the ambient temperature is above 50
℃
.
In order to improve the reliability of the device, do not use the inverter if the ambient temperature changes frequently.
Please provide cooling fan or air conditioner to control the internal ambient temperature below the required one if the inverter is used in a close space such as in the control cabinet.
When the temperature is too low, if the inverter needs to restart to run after a long stop, it is necessary to provide an external heating device to increase the internal temperature,
otherwise damage to the devices may occur.
Humidity
RH
≤
90%
No condensation is allowed.
The maximum relative humidity should be equal to or less than 60% in corrosive air.
Storage
temperature
-40
℃
~
+
70
℃
, and the temperature changing rate is less than 1
℃
/minute.
Running environment
condition
The installation site of the inverter should:
- Keep away from the electromagnetic radiation source
- Keep away from contaminative air, such as corrosive gas, oil mist and flammable gas;
- Ensure foreign objects, such as metal power, dust, oil, water can not enter into the inverter(do not install the inverter on the flammable materials such as wood)
- Keep away from direct sunlight, oil mist, steam and vibration environment.
Altitude
Below 1000m
If the sea level is above 1000m, please derate 1% for every additional 100m.
Vibration
≤
5.8m/s
2
(0.6g)
Installation direction
The inverter should be installed on an upright position to ensure sufficient cooling effect.
Note:
CV10 inverters should be installed in a clean and ventilated environment according to enclosure classification. Cooling air must be clean, free from corrosive materials and electrically conductive dust.
●
Installation space and direction
Note:
CV10 is wall mountable, and the minimum space of A and B is 100mm.