Quick Start Guide of CV10- ControlVIT Series

 

 

2 / 5   

EL086A01 

 

Standard wiring 

Ground the inverter 
Check the ratings of the circuit breaker 
Check whether the motor voltage and power are compatible with those of the inverter 

4.1

 

Main circuit 

 

L N  (+) PB 

 

4.2 Control circuit

 

 

 

Operation and start up 

5.1 Power on 

Power on after checking as followings: 

Checking  

Content 

Voltage of the power supply 

Please check the voltage. Single phase 230V: 

220V(-15%)~240V(+10%) 

Ground the input terminals, L and N, with proper techniques 

Check the inverter and the motor are grounded correctly   

Connection between output 

terminals of the inverter and 

motor terminals 

Please ensure the output terminals of the inverter are 

connected tightly with the motor terminals   

Connection of the terminals 

of control circuit 

Please ensure the terminals of the control circuit are connected 

tightly with other control devices   

Control terminals of the 

inverter 

Please ensure all terminals of the control circuit are on the 

status of OFF 

Loads status 

Please ensure whether the motor is non-load   

Connect the inverter with the motor; Connect the inverter with the power supply 

Terminal 

sign 

Terminal name 

Function  

Power input of the main circuit   

Single phase AC input terminals which are 
generally connected with the power supply. 

The inverter output   

3-phase AC output terminals which are generally 
connected with the motor. 

PB 

Braking resistor terminal 

PB and (+) are connected to the external resistor. 

(+) 

 

Grounding terminal 

Each machine has a standard PE terminal. 

Note:  

 Do not use asymmetrically motor cables. If there is a symmetrically grounding conductor in the motor 

cable in addition to the conductive shield, connect the grounding conductor to the grounding terminal 
at the inverter and motor ends. 

 Route the motor cable, input power cable and control cables separately. 

 C3 optional input filter is parallel-connected with the input of the inverter if selected. 

Terminal 

name 

Description 

ROA 

RO relay output   
Contactor capability: 3A/AC250V, 1A/DC30V 

ROC 

+10V 

Local power 10V 

AI

 

1. Input range: AI voltage and current can be chosen: 0~10V/0~20mA; can be shifted by 
J3 , -10V~+10V   
2. Input impedance: voltage input: 20k

; current input: 500

 

3. Resolution: the minimum one is 5mV when 10V corresponds to 50Hz   
4. Deviation 

±

1%, 25

 

Note: 

the potentiometer sets AI1 parameters and AI terminal sets AI2 parameters. 

AO 

1. Output range: 0~10V or 0~20mA 
2. The voltage or the current output depends on the jumper   
3. Deviation

±

1%,25

 

24V 

Local 24V power supply 

GND 

+10V reference zero potential 

S1 

Switch input 1 

1. Internal impedance: 3.3k

 

2. 0~4V corresponds to low level input and 7~30V 
corresponds to high level input   
3. Max input frequency:1kHz 
4. All are programmable digital input terminal. User can set 
the terminal function through function codes. 

S2 

Switch input 2 

S3 

Switch input 3 

S4 

Switch input 4 

S5 

Switch input 5 

Common terminal for S5 and Y, can be switched by J1 

Note:

 S5 and Y can not be used at the same time. 

Digital output terminal 

485+ 

485 communication interface and 485 differential signal interface 
If it is the standard 485 communication interface, please use twisted pairs or shielded 
cable.  

485- 

 

5.2 Displaying   

The keypad displays as following after power on:   

NO. 

Name  

Content  

Normal 

 

Display the running frequency   

RUN/TUNE LED is on 

Hz LED is on 

Fault 

 

(for example: external fault)   

The displaying is determined by the fault type 

Please refer to the fault solutions of the operation 

manual of CV10 products 

TRIP LED is on 

 

5.3 Parameters setting

 

”: means the set value of the parameter can be modified on stop and running state

 

”: means the set value of the parameter can not be modified on the running state

 

”: means the value of the parameter is the real detection value which can not be modified.

 

Note:

 

Automatic check constraints are available to avoid errors for the modifying of the parameters.   

Code 

Name 

Detailed instruction of parameters 

Default 

value

Modify

P00 Group    Basic function group 

P00.00 

Speed control 

mode 

2:SVPWM control 

 

P00.01  Run command 

channel 

0:Keypad          2:Communication 

1:Terminals 

P00.03 

Max. output 

frequency 

P00.04~400.00Hz 

50.00Hz

 

P00.04 

Upper limit of 

the running 

frequency 

P00.05~P00.03 (Max. output frequency) 

50.00Hz

 

P00.05 

Lower limit of 

the running 

frequency 

0.00Hz~P00.04 (Upper limit of the running frequency) 

0.00Hz 

 

P00.06 

A frequency 

command 

selection 

0:Keypad  

1:Analog AI1(corresponding to keypad potentiometer)   

2:Analog AI2(corresponding to terminal AI1) 

6: Multi-step speed running setting 

7: PID control setting   

8: MODBUS communication setting   

 

P00.07 

B frequency 

command 

selection 

 

P00.08 

B frequency 

command 

reference 

selection 

0: Maximum output frequency   

1: A frequency command   

 

P00.09 

Combination of 

the setting 

source 

0:A

            1:B

                            2:A+B

   

3:A-B      4:Max(A

B):            5:Min(A

B):

 

 

 

P00.10 

Keypad set 

frequency 

Setting range:0.00 Hz~P00.03(the Max. frequency)

 

50.00Hz

P00.11 

ACC time 1 

0.0~3600.0s 

Depends

on model

P00.12 

DEC time 1 

Depends

on model

P00.13 

Running 

direction 

selection 

0: Runs at the default direction 

1: Runs at the opposite direction   

 

P00.14 

Carrier 

frequency 

setting 

1.0~8.0kHz 

4 kHz 

 

P00.16 

AVR function 

selection 

0:Invalid 

1:Valid during the whole procedure 

P00.18 

Function

restore 

parameter 

0:No operation       1:Restore the default value 

2:Clear fault records 

 