Quick Start Guide of CV10- ControlVIT Series

 

 

5 / 5   

EL086A01 

Fault code 

Fault type 

Possible cause 

Solutions 

UV 

DC bus 

Under-voltage 

1. The voltage of the power 

supply is too low. 

2. The overvoltage stall 

protection is not opened. 

1. Check the input power of 

the supply line. 

2. Check the setting of relative 

function codes. 

OL1 Motor 

overload 

1. The voltage of the power 

supply is too low. 

2. The motor setting rated 

current is incorrect.   

3. The motor stall or load 

transients are too strong.   

1. Check the power of the 

supply line   

2. Reset the rated current of 

the motor 

3. Check the load and adjust 

the torque lift 

OL2 Inverter 

overload 

1. The acceleration is too fast 

2. Reset the rotating motor   

3. The voltage of the power 

supply is too low.   

4. The load is too heavy.   

5. Close loop vector control, 

reverse direction of the code 

panel and long low-speed 

operation 

1. Increase the ACC time 

2. Avoid the restarting after 

stopping.  

3. Check the power of the 

supply line 

4. Select an inverter with 

bigger power. 

5. Select a proper motor.   

OL3 Electrical 

overload 

The inverter will report 

overload pre-alarm according 

to the set value.   

Check the load and the 

overload pre-alarm point. 

OH1 Rectifier 

overheat 

1. Air duct jam or fan damage   

2. Ambient temperature is too 

high.  

3. The time of overload 

running is too long.     

1. Refer to the overcurrent 

solution  

2. Redistribute 

dredge the wind channel or 

change the fan   

3. Low the ambient 

temperature  

4. Check and reconnect 

5. Change the power 

6. Change the power unit 

7. Change the main control 

panel 

OH2 IGBT 

overheat 

EF External 

fault 

S1

~

S5 external fault input 

terminals action   

Check the external device 

input  

CE Communication 

error 

1. The baud rate setting is 

incorrect.  

2. Fault occurs to the 

communication wiring. 

1. Set proper baud rate 

2. Check the communication 

connection distribution   

3. Set proper communication 

Fault code 

Fault type 

Possible cause 

Solutions 

3. The communication 

address is wrong. 

4. There is strong interference 

to the communication.   

address.

4. Change or replace the 

connection distribution or 

improve the anti-interference 

capability. 

EEP EEPROM 

fault 

1. Error of controlling the write 

and read of the parameters   

2. Damage to EEPROM   

1. Press STOP/RST to reset

2. Change the main control 

panel 

PIDE 

PID feedback fault 

1. PID feedback offline 

2. PID feedback source 

disappear 

1. Check the PID feedback 

signal 

2. Check the PID feedback 

source 

END 

Time reach of factory 

setting 

The actual running time of the 

inverter is above the internal 

setting running time.   

Ask for the supplier and adjust 

the setting running time.   

LL 

Electronic underload 

fault 

The inverter will report the 

underload pre-alarm 

according to the set value.   

Check the load and the 

underload pre-alarm point.   

Other states 

Fault code 

Fault type 

Possible cause 

Solutions  

PoFF 

System power off 

System power off or low DC voltage  Check the grid 

Fault reset   

The inverter can be reset by STOP/RST, digital input, and power switching-off. After the problems 
settlement, the motor can be restarted.

 

 

 

Only qualified trained people can settle the fault and please do as the “safety precautions”.

 