110
Frequency setting by external terminals
4.7.3
Remote setting function (Pr. 59)
The above parameter can be set when
Pr. 160 Extended function display selection
=
"0"
. (Refer to page 156)
* External running frequency (other than multi-speed) or PU running frequency
NOTE
The
Pr. 15
setting should be equal to or higher than the
Pr. 13 Starting frequency.
Changing the terminal assignment using
Pr.178 to Pr.182 (input terminal function selection)
may affect other functions. Set
parameters after confirming the function of each terminal.
During Jog operation, the second acceleration/deceleration via the RT signal cannot be selected. (The other second
functions are valid.
)
When
Pr. 79
Operation mode selection
= "4", pressing
of the operation panel and
/
of the parameter unit
(FR-PU04/FR-PU07) starts the inverter and pressing
stops the inverter.
This function is invalid when
Pr. 79
= "3".
Parameters referred to
Pr. 13 Starting frequency
Pr. 20 Acceleration/deceleration reference frequency, Pr. 21 Acceleration/deceleration time increments
Pr. 79 Operation mode selection
Pr. 178 to Pr. 182 (input terminal function selection)
Even if the operation panel is located away from the enclosure, you can use contact signals to perform continuous
variable-speed operation, without using analog signals.
By merely setting this parameter, you can use the acceleration, deceleration and setting clear functions of the
remote speed setter (FR-FK).
Parameter
Number
Name
Initial Value
Setting
Range
Description
RH, RM, RL signal
function
Frequency setting
storage function
59
Remote function selection
0
0
Multi-speed setting
—
1
Remote setting
With
2
Remote setting
Not used
3
Remote setting
Not used
(Turning STF/STR OFF
clears remotely-set
frequency.)
Forward rotation
Acceleration
Deceleration
Clear
Inverter
Connection diagram
for remote setting
STF
RH
RM
RL
SD
10
2
5
0
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Deceleration
(RM)
Clear (RL)
Acceleration
(RH)
Forward rotation
(STF)
Power supply
0Hz
Time
Output frequency (Hz)
∗
When
Pr. 59
= 1
When
Pr. 59
= 2, 3
When
Pr. 59
= 1, 2
When
Pr. 59
= 3