Goodrive300
inverters Function codes
80
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
P05 Group Input terminals
P05.00
HDI input
selection
0: High pulse input. See P05.49~P05.54
1: Digital input. See P05.09
0
◎
P05.01
S1
terminals
function
selection
1
◎
P05.02
S2
terminals
function
selection
4
◎
P05.03
S3
terminals
function
selection
7
◎
P05.04
S4
terminals
function
selection
0
◎
P05.05
S5
terminals
function
selection
0
◎
P05.06
S6
terminals
function
selection
0
◎
P05.07
S7
terminals
function
selection
0: No function
1: Forward rotation operation
2: Reverse rotation operation
3: 3-wire control operation
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Operation pause
9: External fault input
10:Increasing frequency setting(UP)
11:Decreasing frequency setting(DOWN)
12:Frequency setting clear
13:Shift between A setting and B setting
14:Shift between combination setting and A setting
15:Shift between combination setting and B setting
16:Multi-step speed terminal 1
17:Multi-step speed terminal 2
18:Multi-step speed terminal 3
19:Multi- step speed terminal 4
20:Multi- step speed pause
21:ACC/DEC time 1
22:ACC/DEC time 2
23:Simple PLC stop reset
24:Simple PLC pause
25:PID control pause
26:Traverse Pause(stop at the current frequency)
27:Traverse reset(return to the center frequency)
0
◎
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...