Goodrive300
inverters Function codes
117
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
P09.10
Output
lower limit
of PID
max. voltage of ( P04.31)
Setting range of P09.09: P09.10~100.0%
Setting range of P09.10: -100.0%~P09.09
0.0%
○
P09.11
Detection
value of
feedback
offline
0.0%
○
P09.12
Detection
time of
feedback
offline
Set the detection value of feedback offline, when
the feedback detection value is smaller than or
equals to the detected value, and the lasting time
exceeds the set value in P09.12, the inverter will
report “PID feedback offline fault” and the keypad
will display PIDE.
Setting range of P09.11: 0.0~100.0%
Setting range of P09.12: 0.0~3600.0s
1.0s
○
P09.13
PID
adjustment
0x00~0x11
LED ones:
0: Keep on integral adjustment when the frequency
achieves the upper and low limit; the integration
shows the change between the reference and the
feedback unless it reaches the internal integral
limit. When the trend between the reference and
the feedback changes, it needs more time to offset
the impact of continuous working and the
integration will change with the trend.
1: Stop integral adjustment when the frequency
achieves the upper and low limit. If the integration
keeps stable, and the trend between the reference
and the feedback changes, the integration will
0x00
○
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...