Goodrive300
inverters Function codes
125
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
ratio during
current limit
output frequency will keep on decreasing to the
lower limit. If the output current is detected to be
lower than the limit level, the inverter will accelerate
to run.
Setting range of P11.06:50.0~200.0%
Setting range of P11.07:0.00~50.00Hz/s
P11.08
Overload
pre-alarm
of
motor/inver
ter
0x000
○
P11.09
Overload
pre-alarm
detection
150%
○
P11.10
Overload
pre-alarm
detection
time
The output current of the inverter or the motor is
above P11.09 and the lasting time is beyond
P11.10, overload pre-alarm will be output.
Setting range of P11.08:
Enable and define the overload pre-alarm of the
inverter or the motor.
Setting range: 0x000~0x131
LED ones:
0:Overload pre-alarm of the motor, relative to the
rated current of the motor
1:Overload pre-alarm of the inverter, relative to the
1.0s
○
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...