Goodrive300
inverters Basic operation instruction
175
Function
code
Name
Detailed instruction of parameters
Default
value
rotation
P01.14
Shifting between
FWD/REV rotation
Set the threshold point of the inverter:
0:Switch after 0 frequency
1:Switch after the starting frequency
2:Switch after the speed reach P01.15
and delay for P01.24
0
P01.15
Stopping speed
0.00~100.00Hz
0.10 Hz
P01.16
Detection of stopping
speed
0: Speed setting (the only detection
method in V/F mode)
1: Speed detecting value
0
P01.17
Detection time of the
feedback speed
Setting range:0.0~100.0s (only valid
when P01.16=1)
0.05s
P01.18
Terminal
running protection when
powering on
0:The terminal running command is
invalid when powering on
1: The terminal running command is
valid when powering on
0
P01.19
Action if running
frequency< lower limit
frequency
(valid >0)
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
0
P01.20
Hibernation restore delay
time
0.0~3600.0s(valid when P01.19=2)
0.0s
P01.21
Restart after power off
0: Disable
1: Enable
0
P01.22
The waiting time of restart
after power off
0.0~3600.0s(valid when P01.21=1)
1.0s
P01.23
Start delay time
0.0~60.0s
0.0s
P05.01~P0
5.09
Digital input function
selection
1: Forward rotation operation
2: Reverse rotation operation
4: Forward rotation jogging
5: Reverse rotation jogging
6: Coast to stop
7: Fault reset
8: Operation pause
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...