Goodrive300
inverters Function codes
74
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
P04.27 to change the feature of the curve.
Note:V
b
in the below picture is the motor rated
voltage and f
b
is the motor rated frequency.
P04.01
Torque
boost of
motor 1
0.0%
○
P04.02
Torque
boost close
of motor 1
Torque boost to the output voltage for the features
of low frequency torque. P04.01 is for the Max.
Output voltage V
b
.
P04.02 defines the percentage of closing frequency
of manual torque to f
b
.
Torque boost should be selected according to the
load. The bigger the load is, the bigger the boost is.
Too big torque boost is inappropriate because the
motor will run with over-magnetic, and the current
of the inverter will increase to raise the temperature
of the inverter and decrease the efficiency.
When the torque boost is set to 0.0%, the inverter
is automatic torque boost.
Torque boost threshold:under the threshold, the
torque boost is valid, but over the threshold, the
torque boost is invalid.
20.0%
○
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...