Goodrive300
inverters Function codes
124
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
e stall
protection
1:Enable
120~150%(standard bus voltage)( 220V)
120%
120~150%(standard bus voltage)(380V)
140%
P11.04
Voltage
protection
of
overvoltage
stall
120~150%(standard bus voltage)( 660V)
120%
○
P11.05
Current
limit action
selection
The actual increasing ratio of motor speed is lower
than the ratio of output frequency because of the
big load during ACC running. It is necessary to take
measures to avoid overcurrent fault and the
inverter trips.
Ones:current limit Setting range of P11.05:
0:Invalid
1:Valid
Tens:overload alarm of hardware current limit (for
factory commissioning)
0: Valid
1: Invalid
01
◎
P11.06
Automatic
current limit
160.0%
◎
P11.07
Frequency-
decreasing
During the running of the inverter, it will detect the
output current and compare it with the limit level
defined in P11.06. If it exceeds the level, the
inverter will run at stable frequency in ACC running,
or the inverter will derate to run during the constant
running. If it exceeds the level continuously, the
10.00H
z/s
◎
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...