![INVT GD300-004G-4 Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/invt/gd300-004g-4/gd300-004g-4_operation-manual_2085739015.webp)
Goodrive300
inverters Product overview
14
Fig 3-3 The simplified main circuit diagram (inverters of 660V)
Note:
1. The inverters of 380V(≥37kW) supports external DC reactors and external braking units,
but it is necessary to remove the copper tag between P1 and(+) before connecting. DC
reactors and external braking units are optional.
2. The inverters of 380V(≤30kW) supports external braking resistors which are optional.
3. The inverters of 660V supports external DC reactors and external braking units, but it is
necessary to remove the copper tag between P1 and(+) before connecting. DC reactors and
external braking units are optional.
3.3 Product specification
Function
Specification
Input voltage (
V
)
AC 3PH 220V(-15%)~240V(+10%)
AC 3PH 380V(-15%)~440V(+10%)
AC 3PH 520V(-15%)~690V(+10%)
Input current (
A
)
Refer to
the
rated value
Power
input
Input frequency (
Hz
)
50Hz or 60Hz
Allowed range: 47~63Hz
Output voltage (
V
)
0~input voltage
Output current (
A
)
Refer to
the rated value
Output power (
kW
)
Refer to
the rated value
Power
output
Output frequency
(
Hz
)
0~400Hz
Control mode
V/F, sensorless vector control
Technical
control
feature
Motor type
Asynchronous motor and permanent magnet
synchronous motor
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...