Goodrive300
inverters Basic operation instruction
184
Function
code
Name
Detailed instruction of parameters
Default
value
P05.54
HDI frequency input filter
time
0.000s~10.000s
0.100s
7.10 Analog output
Goodrive300 series inverters have 2 analog output terminals (0~10V or 0~20mA) and 1 high speed
pulse output terminal. Analog output signal can be filtered and the maximum and minimum values
can be adjusted. The analog output signals can be proportional to motor speed, output frequency,
output current, motor torque, motor power, etc.
Output instructions:
Set value
Function
Instructions
0
Running frequency
0~the Max. output frequency
1
Set frequency
0~ the Max. output frequency
Содержание GD300-004G-4