Control short vibration
Short vibration period and the same set value with the derivative time (Td) mean that the derivative
time is strong. Shortening the derivative time (Td) can control the vibration. When setting the
derivative time as 0.00(ire no derivation control) is useless to control the vibration, decrease the
gain.
Relative parameters list:
Function
code
Name
Detailed instruction of parameters
Default
value
P09.00
PID reference source
0:Keypad (P09.01)
1: AI1
2: AI2
3: AI3
4: HDI
5:Multi-step speed set
6:MODBUS communication set
7:PROFIBUS communication set
8:Ethernet communication set
9:Reserved
0
P09.01
Keypad PID preset
-100.0%~100.0%
0.0%
P09.02
PID feedback source
0: AI1
1: AI2
2: AI3
3: HDI
4:MODBUS communication feedback
5:PROFIBUS communication feedback
0
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...