Goodrive300
inverters Communication protocol
238
running, if the operator clicks sending command bottom, the upper monitor can send
command message actively even it can not receive the message form other devices. In this
case, the upper monitor is the master. And if the designer makes the inverter send the data
only after receiving the command, then the inverter is the slave.
The master can communicate with any single slave or with all slaves. For the single-visiting
command, the slave should feedback a response message; for the broadcasting message
from the master, the slave does not need to feedback the response message.
10.3 Application of the inverter
The Modbus protocol of the inverter is RTU mode and the physical layer is RS485.
10.3.1 RS485
The interface of RS485 works on semiduplex and its data signal applies differential
transmission which is called balance transmission, too. It uses twisted pairs, one of which is
defined as A (+) and the other is defined as B (-). Generally, if the positive electrical level
between sending drive A and B is among +2~+6V, it is logic“1”, if the electrical level is among
-2V~-6V, it is logic“0”.
485+ on the terminal board corresponds to A and 485- to B.
Communication baud rate means the binary bit number in one second. The unit is bit/s (bps).
The higher the baud rate is, the quicker the transmission speed is and the weaker the
anti-interference is. If the twisted pairs of 0.56mm(24AWG)is applied as the communication
cables, the Max. Transmission distance is as below:
Baud rate
Max. transmission
distance
Baud rate
Max. transmission
distance
2400BPS
1800m
9600BPS
800m
4800BPS
1200m
19200BPS
600m
It is recommended to use shield cables and make the shield layer as the grounding wires
during RS485 remote communication.
In the cases with less devices and shorter distance, it is recommended to use 120Ω terminal
resistor as the performance will be weakened if the distance increase even though the
network can perform well without load resistor.
10.3.2.1 Single application
Figure 1 is the site Modbus connection figure of single inverter and PC. Generally, the
computer does not have RS485 interface, the RS232 or USB interface of the computer
should be converted into RS485 by converter. Connect the A terminal of RS485 to the 485+
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...