Goodrive300
inverters Appendix D
297
Follow the manufacturer’s instructions.
It is necessary to install the electromagnetic contactor in the input side to control the
switching on and off safety of the main circuit. It can switch off the input power supply when
syatem fault.
D.5.1 The inverters of AC 3PH 380V(-15%)~440V(+10%)
Model
Breaker (A)
Breaker (A)
The rated working
current of the
contactor(A)
GD300-1R5G-4
15
16
10
GD300-2R2G-4
17.4
16
10
GD300-004G-4
30
25
16
GD300-5R5G-4
45
25
16
GD300-7R5G-4
60
40
25
GD300-011G-4
78
63
32
GD300-015G-4
105
63
50
GD300-018G-4
114
100
63
GD300-022G-4
138
100
80
GD300-030G-4
186
125
95
GD300-037G-4
228
160
120
GD300-045G-4
270
200
135
GD300-055G-4
315
200
170
GD300-075G-4
420
250
230
GD300-090G-4
480
315
280
GD300-110G-4
630
400
315
GD300-132G-4
720
400
380
GD300-160G-4
870
630
450
GD300-200G-4
1110
630
580
GD300-220G-4
1230
800
630
GD300-250G-4
1380
800
700
GD300-280G-4
1500
1000
780
GD300-315G-4
1740
1200
900
GD300-350G-4
1860
1280
960
GD300-400G-4
2010
1380
1035
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...