Goodrive300
inverters Fault tracking
221
OL1
Motor
overload
The voltage of the power
supply is too low
The motor setting rated
current is incorrect
The motor stall or load
transients is too strong
Check the power of the supply
line
Reset the rated current of the
motor
Check the load and adjust the
torque lift
OL2
Inverter
overload
The acceleration is too fast
Reset the rotating motor
The voltage of the power
supply is too low.
The load is too heavy.
Close loop vector control,
reverse direction of the code
panel and long low-speed
operation
Increase the ACC time
Avoid the restarting after
stopping.
Check the power of the supply
line
Select an inverter with bigger
power.
Select a proper motor.
OL3
Electrical
overload
The inverter will report
overload pre-alarm
according to the set value.
Check the load and the overload
pre-alarm point.
SPI
Input phase
loss
Phase loss or fluctuation of
input R,S,T
Check input power
Check installation distribution
SPO
Output phase
loss
U,V,W phase loss input(or
serious asymmetrical three
phase of the load)
Check the output distribution
Check the motor and cable
OH1
Rectifying
module
overheated
OH2
IGBT
overheated
Air duct jam or fan damage
Ambient temperature is too
high.
The time of overload running
is too long.
Refer to the overcurrent solution
Redistribute dredge the wind
channel or change the fan
Low the ambient temperature
Check and reconnect
Change the power
Change the power unit
Change the main control panel
EF
External fault
SI external fault input
terminals action
Check the external device input
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...