Goodrive300
inverters Product overview
18
Model
Rated output
power(kW)
Rated input
current(A)
Rated output
current(A)
GD300-5R5G-4
5.5
19.5
14
GD300-7R5G-4
7.5
25
18.5
GD300-011G-4
11
32
25
GD300-015G-4
15
40
32
GD300-018G-4
18.5
47
38
GD300-022G-4
22
56
45
GD300-030G-4
30
70
60
GD300-037G-4
37
80
75
GD300-045G-4
45
94
92
GD300-055G-4
55
128
115
GD300-075G-4
75
160
150
GD300-090G-4
90
190
180
GD300-110G-4
110
225
215
GD300-132G-4
132
265
260
GD300-160G-4
160
310
305
GD300-200G-4
200
385
380
GD300-220G-4
220
430
425
GD300-250G-4
250
485
480
GD300-280G-4
280
545
530
GD300-315G-4
315
610
600
GD300-350G-4
350
625
650
GD300-400G-4
400
715
720
GD300-500G-4
500
890
860
Note:
1. The input current of inverters 1.5~315kW is detected when the input voltage is 380V and
there is no DC reactors and input/output reactors.
2. The input current of inverters 350~500kW is detected when the input voltage is 380V and
there are input reactors.
3. The rated output current is defined when the output voltage is 380V.
4. The output current can not exceed the rated output current and the output power can not
exceed the rated output power in the voltage range.
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...