Goodrive300
inverters Basic operation instruction
159
When the user selects the user-defined V/F curve function in Goodrive300 series inverters, they
can set the given channel of voltage and frequency and the corresponding ACC/DEC time, or the
two can combinate to form a real-time curve.
Note: the application of V/F curve separation can be used in many cases with various kinds of
power supply of the inverter. But the users should set and adjust the parameters with caution.
Incorrect parameters may cause damage to the inverter.
Function
code
Name
Detailed instruction of parameters
Default
value
P00.00
Speed control mode
0: Sensorless vector control mode 0
(apply to AM and SM)
1: Sensorless vector control mode 1
(applying to AM)
2:V/F control
1
P00.03
Max. output frequency
P00.04~400.00Hz
50.00Hz
P00.04
Upper limit of the running
frequency
P00.05~P00.03
50.00Hz
P00.05
Lower limit of the running
frequency
0.00Hz~P00.04
0.00Hz
P00.11
ACC time 1
0.0~3600.0s
Depend
on model
P00.12
DEC time 1
0.0~3600.0s
Depend
on model
P02.00
Motor type 1
0:Asynchronous motor
1:Synchronous motor
0
P02.02
Rated frequency of
asynchronous motor 1
0.01Hz~P00.03(Max frequency)
50.00
P02.04
Rated voltage of
asynchronous motor 1
0~1200V
Depend
on model
P04.00
Motor 1V/F curve setting
0:Straight line V/F curve
;
applying to the
constant torque load
1:Multi-dots V/F curve
2:1.3
th
power low torque V/F curve
3:1.7
th
power low torque V/F curve
4:2.0
th
power low torque V/F curve
0
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...