Goodrive300
inverters Function codes
76
Functi
on
code
Name
Detailed instruction of parameters
Default
value
Modif
y
rated frequency of motor 1) or P04.05~ P02.16(the
rated frequency of motor 1)
The setting range of P04.08:0.0%~110.0%(the
rated voltage of motor 1)
P04.09
V/F slip
compensati
on gain of
motor 1
This function code is used to compensate the
change of the rotation speed caused by load during
compensation V/F control to improve the rigidity of
the motor. It can be set to the rated slip frequency
of the motor which is counted as below:
△
f=f
b
-n*p/60
Of which, f
b
is the rated frequency of the motor, its
function code is P02.01; n is the rated rotating
speed of the motor and its function code is P02.02
;
p is the pole pair of the motor. 100.0% corresponds
to the rated slip frequency
△
f.
Setting range:0.0~200.0%
0.0%
○
P04.10
Vibration
control
factor at
low
frequency
of motor 1
10
○
P04.11
Vibration
control
factor at
high
frequency
of motor 1
10
○
P04.12
Vibration
control
threshold of
motor 1
In V/F control mode, current fluctuation may occur
to the motor at some frequency, especially the
motor with big power. The motor can not run stably
or overcurrent may occur. These phenomena can
be canceled by adjusting this parameter.
The setting range of P04.10:0~100
The setting range of P04.11:0~100
The setting range of P04.12:0.00Hz~P00.03(the
Max. frequency)
30.00
Hz
○
P04.13 Motor 2 V/F
This group of parameters defines the V/F setting
0
◎
Содержание GD300-004G-4
Страница 1: ...3...
Страница 148: ...Goodrive300 inverters Basic operation instruction 147...
Страница 159: ...Goodrive300 inverters Basic operation instruction 158...
Страница 164: ...Goodrive300 inverters Basic operation instruction 163...
Страница 173: ...Goodrive300 inverters Basic operation instruction 172...
Страница 189: ...Goodrive300 inverters Basic operation instruction 188...
Страница 204: ...Goodrive300 inverters Basic operation instruction 203...
Страница 211: ...Goodrive300 inverters Basic operation instruction 210 convolution is required The working flowchart is as below...
Страница 227: ...Goodrive300 inverters Fault tracking 226 8 6 2 Motor vibration...
Страница 228: ...Goodrive300 inverters Fault tracking 227 8 6 3 Overvoltage 8 6 4 Undervoltage fault...
Страница 312: ...1 1 0 0 1 0 0 7 7 9 C E 66001 00035 201303 V1 4...