Using a UPS or Generator
If the transmitter is backed up with a UPS or generator to keep it operating during an
AC power failure, then the logical thing to do is to lower the transmitter power to
conserve the UPS for as long as possible. Therefore, during an AC power failure, the
transmitter has the ability to automatically operate at a reduced power level when
backed up by a UPS or generator if so desired.
When the UPS is activated, TB1-9 (see "2.7.2 UPS/RFSOURCE Select: Configurable
Input" on page 2-34) on the remote control interface terminal strip must be pulled low.
This will take the transmitter to the preset UPS power level which is factory set for ½
rated power, via software in the Diagnostics Display System. However, if the
transmitter is operating in LOW power when the UPS mode is activated, then the
transmitter will stay at the LOW power level unless the UPS level is set lower. For
example, if LOW power is set for 3kW and UPS is set for 3500W, the transmitter will
stay at the LOW power level of 3kW. If the transmitter is operating at HIGH power
when the UPS mode is activated then it will drop to the UPS power setting.
2.8.1
Setting The UPS Power Level
The setting of the UPS power level is done in the software of the Diagnostics Display
Menu. To set the UPS power level press [HOME, MORE, CONFIGURATION, B, A,
B] then choose the desired modulation format to see Figure 2-17. Once the new UPS
power level is set press [BACK] to save the new information. Pressing [HOME] instead
will cancel any changes made and take you back to the main menu.
Set UPS Power Level for any other desired modulation formats.
Содержание Platinum Z16HD+
Страница 4: ...MRH 2 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...
Страница 6: ...9 15 06 888 2586 001 MRH 1 WARNING Disconnect primary power prior to servicing ...
Страница 8: ...viii 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...
Страница 10: ...x 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...