9/15/06
888-2586-001
2-21
WARNING: Disconnect primary power prior to servicing.
Section 2 Installation & Initial Turn-On
Platinum Z16HD+
2.5.7.2
Three Phase AC Connection
AC connections are made to the top of the AC mains
contactor K1. K1 is on the top right side in the rear of
the cabinet. There is also a large standoff located
near the main contactor for the NEUTRAL
connection in 380VAC (342-432Vac) 4-wire WYE
systems. Bring the AC wires through the holes in the
top of the transmitter and connect to the top
terminals on contactor K1.
!
CAUTION:
THE NEUTRAL CONNECTION IS
EXTREMELY IMPORTANT IN 380VAC 4-WIRE WYE APPLICATIONS. BY
VIRTUE OF THE SINGLE PHASE LOADS WITHIN THE TRANSMITTER, THE
SYSTEM IS NOT ENTIRELY BALANCED, REQUIRING NEUTRAL CURRENT TO
MAINTAIN PROPER PHASE TO NEUTRAL VOLTAGES. A POOR NEUTRAL
CONNECTION COULD CAUSE DAMAGE TO THE SINGLE PHASE ELEMENTS
IN THE TRANSMITTER.
NOTE:
The NEUTRAL connection is NOT required for 208/220VAC 4-wire WYE
source voltage and should not be run to the transmitter. There is no connec-
tion in the transmitter for the neutral connection (for this application) and it
should not be connected to chassis ground. The power supply transformers in the
transmitter will be configured as delta for this application.
2.5.7.3
Single Phase AC Connection
The single phase Z16HD+ requires a dual feed, one to each cabinet. These connect into
the top of the AC mains contactors, 1K1 and 2K1. The two wires should be connected
to the terminals closest to the front of the transmitter. The last terminal (toward the rear)
is not connected.
2.5.7.4
Grounding
A ground strap attachment point is located on the top, right rear, of the cabinet (use four
1/4-20 brass screws with brass washers). Use this connection when utilizing a single
point grounding system, attaching your ground strap to the common grounding plate.
An alternate ground connection is a short copper strap on the back of the Platinum Z
transmitter, on the bottom right side. Unfold this strap and securely bolt or silver solder
Содержание Platinum Z16HD+
Страница 4: ...MRH 2 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...
Страница 6: ...9 15 06 888 2586 001 MRH 1 WARNING Disconnect primary power prior to servicing ...
Страница 8: ...viii 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...
Страница 10: ...x 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...