Section 2 Installation & Initial Turn-On
Platinum Z16HD+
g.
Connect the safety ground wire to the stud on the front of the power supply tray.
h.
Tighten the two hold downs on the front of the power supply tray and replace the
front panels. Power supply installation is complete.
2.5.6.4
Auxiliary Cabinet
Additional connections for single phase power supplies include connecting the
contactor coil and flushing fan AC power. 2A1P3 joins wires 46 and 47 from the PA
cabinet with wires 51 and 52 from the Auxiliary cabinet. See figure 2-3. The fan
assemblies from both cabinets must be removed from the bottom rear to make the
connection.
2.5.7
Transmitter AC Connections
The AC input for the transmitter should be low impedance, 50/60 Hz, 3 phase or dual
feed single phase depending on the type of power supply, with sufficient capacity to
supply the transmitter. For more information see “Power Distribution for Optimum
Transmitter Performance” at the end of this section.
Refer to the “Z16HD+ Outline Drawing” in the drawing package for current ratings,
nominal fuse sizes and wire gauge for the 3 phase 3-wire (delta or wye), 4 wire wye or
single phase input voltage combinations. The AC input wiring should be in agreement
with local electrical codes and capable of supplying the transmitter power requirements.
A customer supplied AC primary power disconnect or means to completely de-energize
the transmitter primary circuit for servicing is necessary.
Harris does not recommend using circuit breakers for this transmitter. The
recommended fuse type is class RK5, a dual element time delay fuse. Examples are the
Bussmann FRN-R (250V), FRS-R (600V), Littelfuse FLNR (250V), FLSR (600V), and
Ferraz gG fuses. If you prefer to use a circuit breaker in your installation, select one
with a motor-starting trip curve, similar to the RK5 curve for fuses. This type of delayed
response is needed in order to accommodate the momentary in-rush current. This can be
300 to 600 amps, depending on the transmitter model and AC configuration.
!
WARNING:
DISCONNECT AND LOCKOUT PRIMARY POWER AT THE AC SOURCE PRIOR TO
PERFORMING ANY CONNECTIONS, REPAIRS, OR MAINTENANCE INSIDE THE
TRASNMITTER.
Содержание Platinum Z16HD+
Страница 4: ...MRH 2 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...
Страница 6: ...9 15 06 888 2586 001 MRH 1 WARNING Disconnect primary power prior to servicing ...
Страница 8: ...viii 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...
Страница 10: ...x 888 2586 001 9 15 06 WARNING Disconnect primary power prior to servicing ...