7 Product-specific CAN objects XN300 slice modules
7.19 XN-322-4AIO-U2
238
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
7.19.4 Analog Input Global Interrupt Enable (Object 0x6423)
Object 0x6423 enables and disables the transmission of data via object
0x6401 in general.
Default value
•
FALSE (0)
Object 0x6401 is not enabled and cannot transmit any analog input val-
ues.
•
TRUE (1)
Object 0x6401 is enabled and can transmit analog input values.
7.19.5 Analog Input Interrupt Upper Limit Integer (Object 0x6424)
Object 0x6424 defines an upper limit and affects the transmission of object
0x6401 accordingly
Object 0x6401 will be transmitted (CAN transmission) if all of the following
conditions are met:
•
The analog input value (ENTRY into 0x6401) is equal to or greater than
the upper limit (Upper Limit 0x6424).
•
Object 0x6421 is set to enable.
Data bit
Desig-
nation
Meaning
0
0 = Upper limit not exceeded
1 = Upper limit exceeded
1
0 = Input not below lower limit
1 = Input below lower limit
2
0 = Input not changed by more than delta
1 = Input changed by more than delta
3
0 = Input not reduced by more than negative delta
1 = Input reduced by more than negative d
4
0 = Input not reduced by more than positive delta
1 = Input reduced by more than positive delta
5 – 7
reserved
Feature
Description / Value
EDS
Name
AnalogInputGlobalInterruptEnable
[MxFixed6423]
ParameterName=AnalogInputGlobalInterruptEnable
ObjectType=0x7
DataType=0x0001
AccessType=rw
DefaultValue=0
PDOMapping=0
Description
Analog Input Global Interrupt Enable
Object Code
Variable
Mapping
SDO
Data type
BOOLEAN
Access
rw
Default value
FALSE
Object Code
Variable
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Страница 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...