3 Commissioning
3.3 LEDs on the device
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
47
GW LED
I/O LED
ST LED
POW-LED
GW LED
Status
Meaning
Green
Continuous
light green
Firmware running properly
off
–
Firmware error or boot loader mode active
I/O LED
Status
Meaning
Green
Continuous light
green
Actual configuration = Target configuration
Flashing
Config check disabled
Red
Continuous light
red
Actual configuration
≠
Target configuration
off
–
Configuration has not been checked yet.
ST LED
Status
Designation
Meaning
Green
Continuous
light green
OPERATIONAL
Process data being transferred
Flashing
PRE-OPERATIONAL
PRE-OPERATIONAL
Flashing
pattern:
SINGLE FLASH
STOPPED
HALT
Red
Continuous
light red
BUS OFF
The field bus has been turned off due to an error, e.g.,
• Wiring faults,
• - Module with wrong baud rate on bus
Flashing
pattern:
SINGLE FLASH
ERROR WARNING
Warning!
• Wiring faults,
• Module with wrong baud rate on bus
Flashing
pattern:
DOUBLE FLASH
Guarding error
Depending on the relevant setting (OD 0x1029), the
gateway will internally switch to the PRE-OPERA-
TIONAL state (default), to the STOPPED state, or will
remain in its current state.
red/green
Flickering
INITIALISATION
Automatic baud rate detection in progress
off
–
CANopen disabled
The field bus has been deactivated. Possible causes
include:
• XN300-Assist wiring test active
• A project is currently being loaded onto the device
POW-LED
Meaning
Green
5 V system bus power working properly
off
No power on system bus
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Страница 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...