7 Product-specific CAN objects XN300 slice modules
7.5 XN-322-20DI-PCNT
124
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
7.5.5 Counter Mode Register (Object 0x4020)
Object 0x4020 can be used to configure the counter inputs and, accordingly,
select the operating mode you want to use. In addition, any writing com-
mand to counter mode register object 0x4020 will reset count registers
0x3023 through 0x3028 to 0x00.
Design of the data bytes:
Byte 0:
Sub-Index 1
≦
n
≦
254
Feature
Description / Value
EDS
Name
Counter Mode Register
[MxSubExt4020]
ParameterName=CounterModeRegister
ObjectType=0x7
DataType=0x0005
AccessType=rw
PDOMapping=0
Count=1
Description
CounterModeRegister
Object Code
VAR
Mapping
SDO
Data type
UNSIGNED8
Sub index
01 … FE
hex
Access
rw
Default value
0x00
hex
7
6
5
4
3
2
1
0
–
–
CLASS
CLASS
CLASS
TYPE
TYPE
TYPE
Data bit
Desig-
nation
Meaning
Notes
0
Input 1/2
0 = Counter Mode
1 = Incremental Encoder Mode
1
Input 3/4
0 = Counter Mode
1 = Incremental Encoder Mode
2 – 7
reserved