1 XN-312-GW-CAN gateway
1.5 Important data for engineering
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
21
Reminder
The following states are defined in CiA301: PRE-OPERATIONAL, OPERA-
TIONAL, STOPPED, and INITIALIZED.
Red
Continuous
light red
BUS OFF
The field bus has been turned off due to an error,
e.g.,
• Wiring faults
• Module with wrong baud rate on bus
Flashing
pattern
SINGLE FLASH
:
Warning!
Errors have occurred on the field bus
Flashing
pattern
DOUBLE FLASH
Error!
GUARD or HEARTBEAT has occurred on the field
bus
Excessive bus load, values for guarding settings
set too low, connection problems.
red/
green
Flickering
Baud rate detection active
off
–
CANopen disabled
CANopen stack disabled.
The following are possible causes:
• XN300-Assist actively running wiring test
• Baud rate detection started
• Error on field bus
Status
Meaning
Explanation
PRE-OPERATIONAL
The device has been started and has checked
in on the CANopen bus
Outputs are not being written to
PDOs are not being written to the master
Inputs are not being read
The device is being initialized for CANopen
OPERATIONAL
The device has been initialized and is active
Outputs are being written to
PDOs are being written to the master
Inputs are being read
STOPPED
Outputs are not being written to
Inputs are not being read
No monitoring active
The device has already been initialized for
CANopen, but is passive
INITIALIZATION
Device booting
As soon as the device's
internal initialization is
complete, the device will
automatically switch to the
PRE-OPERATIONAL state.
ST LED
Status
CANopen status
Meaning
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Страница 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...