7 Product-specific CAN objects XN300 slice modules
7.13 XN-322-16DIO-PC05
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
163
7.13.10 Counter Mode Register (Object 0x4170)
Object 0x4170 can be used to configure the counter inputs and, accordingly,
select the operating mode you want to use. In addition, any writing com-
mand to counter mode register object 0x4170 will reset count registers
0x3172 through 0x3177 to 0x00.
Design of the data bytes:
Byte 0:
Sub-Index 1
≦
n
≦
254
Feature
Description / Value
EDS
Name
CounterModeRegister1
[MxSubExt4170]
ParameterName=CounterModeRegister1
ObjectType=0x7
DataType=0x0005
AccessType=rw
PDOMapping=0
Count=1
Description
Counter Mode Register 1
Object Code
VAR
Mapping
SDO
Data type
UNSIGNED8
Sub index
01 … FE
hex
Access
rw
Default value
0x00
hex
7
6
5
4
3
2
1
0
–
–
–
–
Input 3/4
Input 1/2
Bit
Designation
Description
B1
B0
0
0
Input 1/2
Counter Mode
0
1
Incremental Encoder Mode
1
1
PWM Time Measuring Mode
Bit
Designation
Description
B3
B2
0
0
Input 3/4
Counter Mode
0
1
Incremental Encoder Mode
1
1
PWM Time Measuring Mode