background image

CM

e

2100

G3

M-Bus Metering Gateway for Mobile Network

IntroductIon

CMe2100 is a flexible and cost-effective DIN-mounted M-Bus 

Metering Gateway for Mobile Network. This quick manual 

only applies to generation 3 of the product. For older versions 

of the manual, a complete description of the product or for 

information in other languages, visit the Elvaco AB website, 

http://www.elvaco.com.

1. 

Serial number

2. 

Push button

3. 

M-Bus terminal

4. 

Antenna SMA 

connector

5. 

IR interface

6. 

PWR LED (green)

7. 

ERR LED (red)

8. 

GSM LED (yellow)

9. 

STA LED (blue)

10.  SIM card holder
11.  USB slave connector
12.  USB master connector
13.  Power supply L
14.  Power supply N

MountIng

The CMe2100 is mounted on a DIN-rail. The blue clip on the 

bottom is used to attach and deatach the device. For safety 

reasons, a DIN-rail enclosure must cover the terminals.

SIM card

Insert the SIM card into the SIM card holder (10). Remember 

its registered phone number for later use.

IMPortant

• 

The SIM card should not have any PIN code activated.

• 

The SIM card must have GPRS internet access activated 

for full functionality.

• 

If a prepaid SIM card is used, make sure that it has 

enough credit.

Power SuPPly

Screw terminal (13) and (14) are used to supply the device 

with power. The main supply voltage should be in the range of 

100-240 VAC, with a frequency of 50/60 Hz. The power needs 

to be connected via a clearly marked and easily accessable 

switch to make sure the device can be switched of during 

service work.

IMPortant

• 

The installation should be performed by a qualified 

electrician or another professional with the required 

knowledge.

• 

The power supply must be protected with a 10 A circuit 

breaker of characteristics C or slow blow fuse.

antenna

The included stub antenna is connected to the SMA 

connector (4). If the device is mounted inside a metal cabinet 

or if the signal strength is insufficient (3 or less), an external 

antenna, e.g. LP901, should be used.

IMPortant

• 

CMe2100 should be connected to the antenna when the 

antenna wiring is done. Otherwise the SMA connector 

might be damaged.

• 

Do not mount the antenna close to any metallic objects 

or the M-Bus 2-wire.

M-BuS 2-wIre BuS

M-Bus is a multi-drop 2-wire bus with no polarity. Use a cable 

of area 0.25-1.5 mm

2

, e.g. a standard telephone cable (EKKX 

2x2x0.5) to connect the wiring to the M-Bus terminal (3). Do 

not exceed the maximum cable length of 1000 m.

L
N

When performing a meter installation, a text message will be 

received from the CMe2100 within one minute, confirming 

that the installation has started. The device will send an 

additional text message after the installation has completed, 

informing whether it was successful or not.

Function

SMS command

Perform a meter installation

install n [profile]

Perform a meter installation, and 

delete all previously installed meters

install n [profile] clean

Perform a meter installation, and keep 

all previously installed meters

install n [profile] keep

Request a status report from the 

CMe2100

status

Synchronize time with internet time 

server

timesync

Send momentary meter values via 

e-mail

momreport

Send momentary meter values to a 

specific recipient

momreport email.

[email protected]

Receive momentary meter values 

via sms

momreport 101 

[secondary address]

Receive meter values from the last 

day structured in an Excel file

report 1day 1104 email.

[email protected]

Receive hourly meter values from the 

last day, structured in an Excel file, 

once every day

sch report1 1day 1104

InStallatIon/Send SMS coMMand

CMe2100 is normally configured via SMS commands. Use the 

commands from the table below and send them to the phone 

number of the SIM card. 

n: 

the number of meters to be installed  

[profile]:

 customer specific profile with customized settings 

(which can be ordered from Elvaco). If no profile is specified, 

default settings will be used for the meter. 

[secondary address]:

  the address of the meter, set by the 

manufacturer. 

English

Отзывы: