8 Station variants
8.5 Loading new firmware onto the gateway
364
Gateway XN-312-GW-CAN
06/16 MN050003-DE www.eaton.eu
▶
Switch DIP switches 1 to 5 on the gateway to the OFF position. This will
set the node ID to 0.
▶
Start the gateway with the set node ID of 0.
The gateway will be in update mode.
▶
Use a mini USB cable to connect the XN-312-GW-CAN gateway to your
computer's USB port.
▶
If drivers for the mini USB cable are not installed, install the drivers by
using the following command sequence:
Windows START-> All Programs-> Eaton-> XN300-Assist-> XN-300-GW-
USB driver installation.
▶
Start XN300-Assist.
▶
Open the "?" menu and select the "Updating the Operating System..."
option.
▶
Click on the arrow next to the "Operating system file..." button and select
the new XN300_CANVxxxxxxx.bin firmware file.
▶
Use the drop-down menu for the COM port to select the port on your PC
into which the mini USB cable is plugged.
▶
Start transferring the firmware by clicking on the "Transfer to device" but-
ton.